intermediateFeatured

Breaker Size Chart | NEC 240.6 & Wire Gauge

Check NEC 240.6 breaker sizes and common copper limits: 14 AWG -> 15A, 12 AWG -> 20A, 10 AWG -> 30A; use calculator for 125% loads.

14 min read
Updated 8/4/2026
EleCalculator Team

Quick Answer

Quick Answer: For common copper branch-circuit lookups, 14 AWG -> 15A, 12 AWG -> 20A, and 10 AWG -> 30A under the NEC 240.4(D) small-conductor path. Standard NEC 240.6 breaker ratings commonly checked next include 15, 20, 25, 30, 35, 40, 45, and 50A, then 60A and larger ratings. Use the calculator after this table when continuous loads, conductor derating, motors, HVAC, listed equipment, or local AHJ rules change the answer.

Wire gauge to breaker size — common copper reference:

Wire Gauge Common Max Breaker Reference Use
14 AWG copper 15A Lighting and 15A branch-circuit checks
12 AWG copper 20A General receptacle and 20A branch-circuit checks
10 AWG copper 30A 30A appliance, HVAC, and equipment checks
8 AWG copper 40A, then calculator review Larger loads where terminal rating and derating matter
6 AWG copper 55A, often 60A with applicable next-size review Feeders and larger equipment where the NEC path must be verified

Run the Breaker Sizing Calculator when the question is not a simple wire-gauge lookup. A general branch circuit, a motor circuit, an equipment-nameplate circuit, and a panel-capacity question do not use the same decision flow.


Breaker Calculator Follow-Up After the Table

Use this sequence after the direct table lookup when the job has conditions that can change the breaker result:

  1. Run the Breaker Sizing Calculator with load current, continuous-duty status, load type, and conductor count.
  2. If the question starts with a conductor or wire gauge, open the Wire Size Calculator and keep voltage drop, material, insulation, and terminal temperature with the result.
  3. If ambient heat, conductor grouping, or terminal rating changes the usable current, verify the Ampacity Calculator before selecting the breaker.
  4. Use the Breaker Size Chart only after the calculator path identifies the load category, conductor basis, and standard OCPD review point.

The NEC 240.6 and wire-gauge tables below are reference checks. They are not a standalone breaker-size finder for motors, HVAC equipment, EVSE, transformers, listed equipment, or panel-capacity changes.


NEC 240.6 Standard Breaker Sizes Reference

Standard Ampere Ratings

Use this table as a reference for standard OCPD ratings after the applicable NEC path is known. Some adopted editions and product categories include additional ratings, so always confirm the code edition and equipment listing before final selection.

Common standard OCPD ratings checked under NEC 240.6(A) include:

Category Available Sizes
Small 15, 20, 25, 30, 35, 40, 45, 50 A
Medium 60, 70, 80, 90, 100, 110, 125 A
Large 150, 175, 200, 225, 250, 300 A
Extra Large 350, 400, 450, 500, 600 A
Industrial 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000, 6000 A

Key Rule: The next-standard-size review is conditional. Only round up when the applicable NEC path, conductor size, equipment listing, and AHJ review allow it.


NEC 240.4 Conductor Protection Table

Maximum Overcurrent Protection for Copper Conductors

Based on NEC Table 310.16, 60°C column (most common for residential; 75°C column applies when terminals are listed for 75°C):

AWG Ampacity (60°C) Max Breaker Max Breaker (Next Size Up Rule)
18 7A 7A* Not typically used
16 10A 10A* Not typically used
14 15A 15A 15A (small conductors exception)
12 20A 20A 20A (small conductors exception)
10 30A 30A 30A (small conductors exception)
8 40A 40A 45A
6 55A 55A 60A
4 70A 70A 70A
3 85A 85A 90A
2 95A 95A 100A
1 110A 110A 110A
1/0 125A 125A 125A
2/0 145A 145A 150A
3/0 165A 165A 175A
4/0 195A 195A 200A

NEC 240.4(D) Small Conductor Exception: 14, 12, and 10 AWG copper conductors are commonly limited to 15A, 20A, and 30A respectively. Do not apply the next-standard-size-up rule until the adopted NEC path, conductor size, and equipment instructions support it.


Maximum Overcurrent Protection for Aluminum Conductors

Based on NEC Table 310.16, 75°C column (aluminum conductors, USE-2, XHHW-2, THHN/THWN-2):

Note: Most equipment terminals are rated 75°C, so the 75°C column applies for most aluminum installations. Aluminum conductors must be terminated in connectors listed for aluminum. Anti-oxidant compound required per manufacturer instructions.

AWG / kcmil Ampacity (75°C) Max OCPD Equivalent Copper Common Use
10 AWG Al 30A 30A 8 AWG Cu Not recommended for 30A branch circuits
8 AWG Al 40A 40A 6 AWG Cu Range, dryer (with Al-rated connectors)
6 AWG Al 50A 50A 4 AWG Cu Subpanel feeder, large A/C
4 AWG Al 65A 65A 3 AWG Cu Service entrance, feeder
2 AWG Al 90A 90A 1 AWG Cu 100A service entrance
1/0 AWG Al 120A 120A 2/0 AWG Cu 125A service
2/0 AWG Al 135A 150A* 3/0 AWG Cu 150A service
4/0 AWG Al 180A 200A* 350 kcmil Cu 200A service entrance
350 kcmil Al 255A 300A* 500 kcmil Cu 300A service
500 kcmil Al 310A 350A* 700 kcmil Cu 350A service

Next standard size up per NEC 240.4(B) when ampacity doesn't match a standard OCPD rating.

Why aluminum conductors are common for service entrances: Aluminum is lighter, less expensive, and has lower thermal expansion concerns when properly terminated. However, aluminum should not be used for small branch circuits unless the adopted NEC edition, product listing, and termination equipment explicitly support the installation. Large aluminum service, feeder, and branch-circuit conductors require proper conductor sizing, compatible terminations, antioxidant practices where specified, and torque verification.


Wire Gauge to Breaker Size Chart

Quick Reference: Copper Wire at 60°C

Wire Size Description Max Breaker Typical Application
14 AWG Smallest residential 15A Lighting, low-load outlets
12 AWG Standard residential 20A General purpose receptacles
10 AWG Heavy duty 30A Dryers, A/C units, water heaters
8 AWG Large loads 40A Electric ranges, large A/C
6 AWG Subfeeder 55A (or 60A*) Subpanels, large equipment
4 AWG Service 70A Small service entrance
3 AWG Service 85A (or 90A*) Service entrance
2 AWG Service 95A (or 100A*) 100A service
1/0 AWG Large service 125A 125A service
2/0 AWG Large service 145A (or 150A*) 150A service
4/0 AWG Residential main 195A (or 200A*) 200A service

*Next standard size up per NEC 240.4(B), when ampacity doesn't match standard breaker size.


Temperature Correction Factor Table

NEC Table 310.15(B)(1) - Ambient Temperature Correction

For ambient temperatures above 30°C (86°F), derate conductor ampacity:

Ambient Temp °C Ambient Temp °F 60°C Conductor 75°C Conductor 90°C Conductor
21-25 70-77 1.08 1.05 1.04
26-30 79-86 1.00 1.00 1.00
31-35 88-95 0.91 0.94 0.96
36-40 97-104 0.82 0.88 0.91
41-45 106-113 0.71 0.82 0.87
46-50 115-122 0.58 0.75 0.82
51-55 124-131 0.41 0.67 0.76
56-60 133-140 0.58 0.71

Formula:

Corrected Ampacity = Base Ampacity × Temperature Correction Factor

Example: 12 AWG (20A at 60°C) in 40°C ambient:

Corrected = 20A × 0.82 = 16.4A → Use 15A breaker

Conductor Fill Derating Table

NEC Table 310.15(C)(1) - More Than 3 Current-Carrying Conductors

Number of Conductors Ampacity Adjustment
4-6 80%
7-9 70%
10-20 50%
21-30 45%
31-40 40%
41 and above 35%

Formula:

Derated Ampacity = Base Ampacity × Fill Adjustment Factor

Example: 12 AWG with 6 conductors in conduit:

Derated = 20A × 0.80 = 16A → Use 15A breaker

Continuous vs Non-Continuous Load Sizing

NEC 210.20(A) Branch Circuit Sizing

Load Type Sizing Rule Formula
Non-continuous 100% of load Breaker ≥ Load
Continuous (3+ hours) 125% of load Breaker ≥ Load × 1.25
Mixed Sum of factors Breaker ≥ (Cont × 1.25) + Non-cont

Calculator handoff: Enter the continuous and non-continuous portions separately in the breaker sizing calculator. Use the adjusted result with the standard-size reference only after the load category is clear.


Residential Breaker Sizing Chart

Common Residential Circuits

Circuit Wire Size Breaker Notes
Lighting 14 AWG 15A Max 12 outlets per circuit
General receptacles 12 AWG 20A Max 10 outlets per circuit
Kitchen counter 12 AWG 20A Two 20A circuits required
Bathroom 12 AWG 20A Dedicated or shared per code
Laundry 12 AWG 20A Dedicated circuit required
Dishwasher 12 AWG 20A Dedicated circuit
Disposal 12 AWG 20A May share with dishwasher
Refrigerator 12 AWG 20A Dedicated recommended
Microwave 12 AWG 20A Dedicated circuit
Electric dryer 10 AWG 30A 30A 4-wire circuit
Electric range 8/6 AWG 40-50A Based on nameplate
Water heater 10 AWG 30A Typical 4500W unit
A/C (small) 10 AWG 30A Check unit nameplate
A/C (large) 8 AWG 40A Check unit nameplate
EV charger L2 6 AWG 50A 40A continuous load

→ Calculate your load first: Residential Load Calculator


Motor Circuit Breaker Sizing

NEC 430.52 Motor Branch Circuit Protection

Motor Type Maximum Breaker Size
Standard induction 250% of FLC
Wound rotor 150% of FLC
Synchronous 200% of FLC
DC (constant voltage) 150% of FLC
DC (variable voltage) 150% of FLC

Motor FLC Reference (3-Phase, 460V):

HP FLC (A) Max Breaker (250%)
1 2.1 6A
3 4.8 15A
5 7.6 20A
7.5 11 30A
10 14 35A
15 21 60A
20 27 70A
25 34 90A
30 40 100A
40 52 150A
50 65 175A
75 96 250A
100 124 350A

→ Use Full Load Current Calculator for NEC table FLC values.


Calculator Workflow Examples

Example 1: Basic Residential Circuit

Try this path: General branch circuit, normal indoor ambient, copper conductor, known circuit rating.

Run the load basis through the Breaker Sizing Calculator, then verify conductor ampacity and terminal rating before treating the branch-circuit breaker as selected.

Example 2: Hot Attic Installation

Try this path: Existing conductor in a hot attic where ambient temperature changes the ampacity basis.

Use the Ampacity Calculator first, then return to the breaker workflow with the adjusted ampacity rather than selecting from the unadjusted conductor row.

Example 3: Conduit with Multiple Conductors

Try this path: Raceway with more than three current-carrying conductors.

Use the Conduit Fill Calculator and Ampacity Calculator before coordinating the breaker with the adjusted conductor result.


Common Mistakes to Avoid

Mistake Why It's Wrong Correct Approach
Using 75°C ratings with 60°C terminals Terminal limits conductor rating Use 60°C column for most residential
Ignoring continuous load 125% rule Breaker will trip Size for 125% of continuous loads
Forgetting conduit fill derating Overheated conductors Apply fill factors when >3 conductors
Using next-size-up for small conductors NEC 240.4(D) prohibits this 14/12/10 AWG limited to 15/20/30A max

AFCI and GFCI Requirements

NEC 210.12 — Arc-Fault Circuit Interrupter (AFCI) Protection

Common NEC 210.12 AFCI review covers 120V, single-phase, 15A and 20A branch circuits supplying outlets or devices in many dwelling-unit locations:

Location AFCI Required NEC Reference
Bedrooms (all) ✔ Yes 210.12(A)(1) — original requirement
Living rooms, parlors, dens ✔ Yes 210.12(A)(2)
Dining rooms, family rooms ✔ Yes 210.12(A)(3)
Kitchens ✔ Yes 210.12(A)(4)
Laundry areas ✔ Yes 210.12(A)(5)
Sunrooms, recreation rooms ✔ Yes 210.12(A)(6)
Hallways, closets ✔ Yes 210.12(A)(7)
Basements (finished) ✔ Yes 210.12(A)(8)
Dormitory units, hotel guest rooms ✔ Yes 210.12(B)
Garages, outdoors, bathrooms ✖ No (GFCI instead) GFCI per 210.8 applies

AFCI breaker types: Combination-type AFCI detects both series and parallel arcing. Branch/feeder AFCI breakers and AFCI receptacles may be permitted depending on the adopted NEC edition, product listing, installation method, and AHJ interpretation. Verify the adopted NEC 210.12 language before choosing the protection method.

NEC 210.8 — Ground-Fault Circuit Interrupter (GFCI) Protection

Common NEC 210.8 GFCI review covers 125V through 250V, single-phase, 15A through 50A receptacles in many dwelling-unit locations:

Location GFCI Required Voltage/Amperage NEC Reference
Bathrooms (all) ✔ Yes 125–250V, 15–50A 210.8(A)(1)
Garages (including attached) ✔ Yes 125–250V, 15–50A 210.8(A)(2)
Outdoors ✔ Yes 125–250V, 15–50A 210.8(A)(3)
Crawl spaces (≤grade level) ✔ Yes 125–250V 210.8(A)(4)
Unfinished basements ✔ Yes 125–250V 210.8(A)(5)
Kitchens (countertop within 6 ft of sink) ✔ Yes 120V, 15/20A 210.8(A)(6)
Kitchen islands and peninsulas ✔ Yes 120V 210.8(A)(7)
Boathouses ✔ Yes 125–250V 210.8(A)(8)
Bathtub and shower areas ✔ Yes 125–250V 210.8(A)(9)
Laundry areas ✔ Yes 125–250V 210.8(A)(10)
Indoor damp/wet locations ✔ Yes 125–250V 210.8(A)(11)
Dishwashers (dedicated circuits) ✔ Yes 120V 210.8(D)
EV charging (in garages) ✔ Yes 125–250V 210.8(A)(2) applies

AFCI vs GFCI: Class A GFCI devices used for personnel protection are intended to trip at low ground-fault current levels, commonly around 5 mA; equipment-protection devices can use higher thresholds. AFCI protects against arcing faults in wiring that may not trip standard breakers. Device class, product listing, adopted NEC edition, and AHJ requirements control the final protection method.


Related Calculators

Calculator Use When...
Breaker Sizing Calculator Screening a standard breaker review point
Wire Size Calculator Determining conductor size for load
Ampacity Calculator Checking conductor ampacity after temperature or conductor-count adjustment
Residential Load Calculator Calculating total service load
Voltage Drop Calculator Checking wire length adequacy

After the Breaker Chart Lookup

Use the chart result as a screening point, not as the final project record. Before updating a panel schedule or selecting equipment, carry the same load basis through the Breaker Sizing Calculator and document the standard-size choice in the Breaker Size Chart. If conductor temperature rating, ambient temperature, or more than three current-carrying conductors changes the ampacity basis, review the NEC Ampacity Chart and run the adjusted value through the Ampacity Calculator before treating the breaker and conductor pair as coordinated. If the work changes an existing panel, update the Panel Load Schedule Chart so circuit identity, breaker poles, spare spaces, and panel limitations stay visible.

When the breaker serves equipment with an interrupting-rating or SCCR question, continue to the Short Circuit Calculator before treating the breaker selection as complete. Field installation still depends on the adopted NEC edition, listed equipment instructions, conductor terminal ratings, available fault current, and AHJ review.


Summary

Use this page as a workflow, not a standalone permission table:

  • Identify whether the breaker protects a general branch circuit, motor, listed equipment, feeder, or panel change.
  • Separate continuous and non-continuous load portions before choosing a standard rating.
  • Confirm conductor material, terminal temperature rating, ambient temperature, and conductor-count adjustment.
  • Use the standard-size, small-conductor, and ampacity references only after the calculator path identifies the project basis.

FAQ

What size wire do I need for a 30 amp breaker?

Enter the load, conductor material, terminal temperature rating, ambient conditions, and run length in the wire-size and ampacity calculators before selecting a conductor. A reference row is not enough when voltage drop, temperature, or conductor count changes the basis.

Can I use a 20 amp breaker on 14 gauge wire?

Treat this as a small-conductor protection check. Use the breaker workflow and the NEC 240.4(D) reference table rather than overriding the conductor-protection path from a single answer snippet.

What is the next size up rule?

NEC 240.4(B) can allow a next standard OCPD rating when the conductor ampacity does not exactly match a standard size, but only when the applicable conditions are satisfied. Use the breaker calculator result with the conductor-protection notes before applying it.

Why does continuous load require 125% sizing?

Continuous loads (running 3+ hours) generate sustained heat in conductors and breakers. The 125% factor provides thermal margin to prevent nuisance tripping and extends equipment life.

How do I size a breaker for multiple loads?

Enter continuous and non-continuous portions separately, then carry the adjusted current into the standard-size and conductor-protection review. The correct result also depends on conductor ampacity, equipment labeling, available fault current, and the adopted NEC edition.

Tags

NECbreaker sizingovercurrent protectioncircuit protection

Related Calculators

Frequently Asked Questions

What size breaker do I need for 12 gauge wire?
For the common copper small-conductor lookup, 12 AWG is limited to a 20A maximum breaker under the NEC 240.4(D) path. Still check terminal temperature rating, conductor material, ambient conditions, conductor count, equipment instructions, and local AHJ rules before using that row for an installation.
What size breaker do I need for 14 gauge wire?
For the common copper small-conductor lookup, 14 AWG maps to a 15A maximum breaker under NEC 240.4(D). Do not use a 20A breaker on 14 AWG copper branch-circuit wiring unless a specific listed-equipment rule and the adopted code path clearly allow a different conductor-protection basis.
What size wire do I need for a 30 amp breaker?
The common copper lookup is 10 AWG for a 30A breaker on the NEC 240.4(D) small-conductor path. Use the wire-size and ampacity calculators when voltage drop, aluminum conductors, temperature correction, more than three current-carrying conductors, or equipment markings change the basis.
What is the NEC 240.4(D) small conductor protection rule?
NEC 240.4(D) keeps common small conductors on a separate protection path from the next-standard-size rule: 14 AWG copper is commonly limited to 15A, 12 AWG to 20A, and 10 AWG to 30A before any equipment-specific or local rule is considered.
How do I size a breaker for a continuous load?
For a basic branch-circuit screen, multiply the continuous portion by 125%, add the non-continuous portion at 100%, then choose a standard NEC 240.6 rating at or above that result. Example: 16A continuous -> 20A before conductor and equipment checks.

Need to Calculate Something?

Use our electrical calculators to solve your engineering problems quickly and accurately.