intermediateFeatured

Standard Breaker Sizes | NEC 240.6 Chart

Use standard breaker sizes from NEC 240.6: 15A, 20A, 25A, 30A, 35A, 40A and 50A; check 14/12/10 AWG and 125% loads.

14 min read
Updated 6/14/2026
EleCalculator Team

Quick Answer

Wire gauge to breaker size — NEC 240.4(D) hard limits:

Match breaker to wire ampacity per NEC 240.4:

NEC standard breaker sizes start at 15, 20, 25, 30, 35, 40, 45, and 50 A before stepping into 60 A and larger ratings under NEC 240.6.

Wire Gauge Max Breaker (Copper, 60°C) Common Use
14 AWG 15A Lighting circuits
12 AWG 20A Receptacle circuits
10 AWG 30A Small appliances, A/C
8 AWG 40A Electric range, dryer
6 AWG 55A Large appliances
4 AWG 70A Subpanels
2 AWG 95A Service entrance

Use the Breaker Sizing Calculator for your specific load.


NEC 240.6 Standard Breaker Sizes

Standard Ampere Ratings

NEC 240.6(A) defines standard circuit breaker sizes:

Category Available Sizes
Small 15, 20, 25, 30, 35, 40, 45, 50 A
Medium 60, 70, 80, 90, 100, 110, 125 A
Large 150, 175, 200, 225, 250, 300 A
Extra Large 350, 400, 450, 500, 600 A
Industrial 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000, 6000 A

Key Rule: Select the next standard size UP if calculated ampacity falls between standard ratings (per NEC 240.4(B)).


NEC 240.4 Conductor Protection Table

Maximum Overcurrent Protection for Copper Conductors

Based on NEC Table 310.16, 60°C column (most common for residential; 75°C column applies when terminals are listed for 75°C):

AWG Ampacity (60°C) Max Breaker Max Breaker (Next Size Up Rule)
18 7A 7A* Not typically used
16 10A 10A* Not typically used
14 15A 15A 15A (small conductors exception)
12 20A 20A 20A (small conductors exception)
10 30A 30A 30A (small conductors exception)
8 40A 40A 45A
6 55A 55A 60A
4 70A 70A 70A
3 85A 85A 90A
2 95A 95A 100A
1 110A 110A 110A
1/0 125A 125A 125A
2/0 145A 145A 150A
3/0 165A 165A 175A
4/0 195A 195A 200A

NEC 240.4(D) Small Conductor Exception: 14, 12, and 10 AWG must NOT exceed 15A, 20A, and 30A respectively. The next-standard-size-up rule (240.4(B)) only applies to conductors 8 AWG and larger.


Maximum Overcurrent Protection for Aluminum Conductors

Based on NEC Table 310.16, 75°C column (aluminum conductors, USE-2, XHHW-2, THHN/THWN-2):

Note: Most equipment terminals are rated 75°C, so the 75°C column applies for most aluminum installations. Aluminum conductors must be terminated in connectors listed for aluminum. Anti-oxidant compound required per manufacturer instructions.

AWG / kcmil Ampacity (75°C) Max OCPD Equivalent Copper Common Use
10 AWG Al 30A 30A 8 AWG Cu Not recommended for 30A branch circuits
8 AWG Al 40A 40A 6 AWG Cu Range, dryer (with Al-rated connectors)
6 AWG Al 50A 50A 4 AWG Cu Subpanel feeder, large A/C
4 AWG Al 65A 65A 3 AWG Cu Service entrance, feeder
2 AWG Al 90A 90A 1 AWG Cu 100A service entrance
1/0 AWG Al 120A 120A 2/0 AWG Cu 125A service
2/0 AWG Al 135A 150A* 3/0 AWG Cu 150A service
4/0 AWG Al 180A 200A* 350 kcmil Cu 200A service entrance
350 kcmil Al 255A 300A* 500 kcmil Cu 300A service
500 kcmil Al 310A 350A* 700 kcmil Cu 350A service

Next standard size up per NEC 240.4(B) when ampacity doesn't match a standard OCPD rating.

Why aluminum conductors are common for service entrances: Aluminum is lighter, less expensive, and has lower thermal expansion concerns when properly terminated. However, aluminum must NEVER be used for small branch circuits (12 AWG or smaller) due to connection failure risks from thermal cycling and oxidation. The 2026 NEC permits aluminum for services, feeders, and large branch circuits (≥8 AWG) with proper terminations.


Wire Gauge to Breaker Size Chart

Quick Reference: Copper Wire at 60°C

Wire Size Description Max Breaker Typical Application
14 AWG Smallest residential 15A Lighting, low-load outlets
12 AWG Standard residential 20A General purpose receptacles
10 AWG Heavy duty 30A Dryers, A/C units, water heaters
8 AWG Large loads 40A Electric ranges, large A/C
6 AWG Subfeeder 55A (or 60A*) Subpanels, large equipment
4 AWG Service 70A Small service entrance
3 AWG Service 85A (or 90A*) Service entrance
2 AWG Service 95A (or 100A*) 100A service
1/0 AWG Large service 125A 125A service
2/0 AWG Large service 145A (or 150A*) 150A service
4/0 AWG Residential main 195A (or 200A*) 200A service

*Next standard size up per NEC 240.4(B), when ampacity doesn't match standard breaker size.


Temperature Correction Factor Table

NEC Table 310.15(B)(1) - Ambient Temperature Correction

For ambient temperatures above 30°C (86°F), derate conductor ampacity:

Ambient Temp °C Ambient Temp °F 60°C Conductor 75°C Conductor 90°C Conductor
21-25 70-77 1.08 1.05 1.04
26-30 79-86 1.00 1.00 1.00
31-35 88-95 0.91 0.94 0.96
36-40 97-104 0.82 0.88 0.91
41-45 106-113 0.71 0.82 0.87
46-50 115-122 0.58 0.75 0.82
51-55 124-131 0.41 0.67 0.76
56-60 133-140 0.58 0.71

Formula:

Corrected Ampacity = Base Ampacity × Temperature Correction Factor

Example: 12 AWG (20A at 60°C) in 40°C ambient:

Corrected = 20A × 0.82 = 16.4A → Use 15A breaker

Conductor Fill Derating Table

NEC Table 310.15(C)(1) - More Than 3 Current-Carrying Conductors

Number of Conductors Ampacity Adjustment
4-6 80%
7-9 70%
10-20 50%
21-30 45%
31-40 40%
41 and above 35%

Formula:

Derated Ampacity = Base Ampacity × Fill Adjustment Factor

Example: 12 AWG with 6 conductors in conduit:

Derated = 20A × 0.80 = 16A → Use 15A breaker

Continuous vs Non-Continuous Load Sizing

NEC 210.20(A) Branch Circuit Sizing

Load Type Sizing Rule Formula
Non-continuous 100% of load Breaker ≥ Load
Continuous (3+ hours) 125% of load Breaker ≥ Load × 1.25
Mixed Sum of factors Breaker ≥ (Cont × 1.25) + Non-cont

Example Calculation:

Load Type Calculation
16A lighting Continuous 16 × 1.25 = 20A
8A receptacles Non-continuous 8 × 1.00 = 8A
Total 28A → 30A breaker

Residential Breaker Sizing Chart

Common Residential Circuits

Circuit Wire Size Breaker Notes
Lighting 14 AWG 15A Max 12 outlets per circuit
General receptacles 12 AWG 20A Max 10 outlets per circuit
Kitchen counter 12 AWG 20A Two 20A circuits required
Bathroom 12 AWG 20A Dedicated or shared per code
Laundry 12 AWG 20A Dedicated circuit required
Dishwasher 12 AWG 20A Dedicated circuit
Disposal 12 AWG 20A May share with dishwasher
Refrigerator 12 AWG 20A Dedicated recommended
Microwave 12 AWG 20A Dedicated circuit
Electric dryer 10 AWG 30A 30A 4-wire circuit
Electric range 8/6 AWG 40-50A Based on nameplate
Water heater 10 AWG 30A Typical 4500W unit
A/C (small) 10 AWG 30A Check unit nameplate
A/C (large) 8 AWG 40A Check unit nameplate
EV charger L2 6 AWG 50A 40A continuous load

→ Calculate your load first: Residential Load Calculator


Motor Circuit Breaker Sizing

NEC 430.52 Motor Branch Circuit Protection

Motor Type Maximum Breaker Size
Standard induction 250% of FLC
Wound rotor 150% of FLC
Synchronous 200% of FLC
DC (constant voltage) 150% of FLC
DC (variable voltage) 150% of FLC

Motor FLC Reference (3-Phase, 460V):

HP FLC (A) Max Breaker (250%)
1 2.1 6A
3 4.8 15A
5 7.6 20A
7.5 11 30A
10 14 35A
15 21 60A
20 27 70A
25 34 90A
30 40 100A
40 52 150A
50 65 175A
75 96 250A
100 124 350A

→ Use Full Load Current Calculator for NEC table FLC values.


Worked Examples

Example 1: Basic Residential Circuit

Given: 20A kitchen counter circuit at 75°F ambient

Solution:

  1. Load: 20A (continuous - kitchen lighting/appliances)
  2. Continuous load factor: 20A × 1.25 = 25A
  3. Wire selection: 10 AWG (30A capacity) to handle 25A
  4. Breaker: 20A (circuit is designated 20A, wire supports it)

Example 2: Hot Attic Installation

Given: 12 AWG wire in 120°F (49°C) attic

Solution:

  1. Base ampacity: 20A (12 AWG, 60°C)
  2. Temperature correction (46-50°C): 0.58
  3. Corrected ampacity: 20A × 0.58 = 11.6A
  4. Maximum breaker: 10A (or use 75°C rated wire with 25A × 0.75 = 18.75A → 15A breaker)

Example 3: Conduit with Multiple Conductors

Given: 6 current-carrying 12 AWG conductors in conduit

Solution:

  1. Base ampacity: 20A
  2. Conductor fill factor (4-6): 0.80
  3. Adjusted ampacity: 20A × 0.80 = 16A
  4. Maximum breaker: 15A

Common Mistakes to Avoid

Mistake Why It's Wrong Correct Approach
Using 75°C ratings with 60°C terminals Terminal limits conductor rating Use 60°C column for most residential
Ignoring continuous load 125% rule Breaker will trip Size for 125% of continuous loads
Forgetting conduit fill derating Overheated conductors Apply fill factors when >3 conductors
Using next-size-up for small conductors NEC 240.4(D) prohibits this 14/12/10 AWG limited to 15/20/30A max

AFCI and GFCI Requirements

NEC 210.12 — Arc-Fault Circuit Interrupter (AFCI) Protection (2026 NEC)

AFCI protection is required for all 120V, single-phase, 15A and 20A branch circuits supplying outlets in the following dwelling unit locations:

Location AFCI Required NEC Reference
Bedrooms (all) ✔ Yes 210.12(A)(1) — original requirement
Living rooms, parlors, dens ✔ Yes 210.12(A)(2)
Dining rooms, family rooms ✔ Yes 210.12(A)(3)
Kitchens ✔ Yes 210.12(A)(4)
Laundry areas ✔ Yes 210.12(A)(5)
Sunrooms, recreation rooms ✔ Yes 210.12(A)(6)
Hallways, closets ✔ Yes 210.12(A)(7)
Basements (finished) ✔ Yes 210.12(A)(8)
Dormitory units, hotel guest rooms ✔ Yes 210.12(B)
Garages, outdoors, bathrooms ✖ No (GFCI instead) GFCI per 210.8 applies

AFCI breaker types: Combination-type AFCI (detects both series and parallel arcing) is the type required by NEC 210.12. Branch/feeder AFCI breakers also satisfy the requirement. AFCI receptacles may be used at the first outlet in lieu of a panel breaker in retrofit situations per 210.12(D). The 2026 NEC extends AFCI to virtually all living spaces in a dwelling unit.

NEC 210.8 — Ground-Fault Circuit Interrupter (GFCI) Protection (2026 NEC)

GFCI protection is required for all 125V through 250V, single-phase, 15A through 50A receptacles in the following locations:

Location GFCI Required Voltage/Amperage NEC Reference
Bathrooms (all) ✔ Yes 125–250V, 15–50A 210.8(A)(1)
Garages (including attached) ✔ Yes 125–250V, 15–50A 210.8(A)(2)
Outdoors ✔ Yes 125–250V, 15–50A 210.8(A)(3)
Crawl spaces (≤grade level) ✔ Yes 125–250V 210.8(A)(4)
Unfinished basements ✔ Yes 125–250V 210.8(A)(5)
Kitchens (countertop within 6 ft of sink) ✔ Yes 120V, 15/20A 210.8(A)(6)
Kitchen islands and peninsulas ✔ Yes 120V 210.8(A)(7)
Boathouses ✔ Yes 125–250V 210.8(A)(8)
Bathtub and shower areas ✔ Yes 125–250V 210.8(A)(9)
Laundry areas ✔ Yes 125–250V 210.8(A)(10)
Indoor damp/wet locations ✔ Yes 125–250V 210.8(A)(11)
Dishwashers (dedicated circuits) ✔ Yes 120V 210.8(D)
EV charging (in garages) ✔ Yes 125–250V 210.8(A)(2) applies

AFCI vs GFCI: GFCI protects against ground faults (≥30 mA leakage to ground → trip within ~25 ms). AFCI protects against arcing faults in wiring that may not trip standard breakers. Both protections can be combined in a dual-function AFCI/GFCI breaker (one device satisfies both NEC 210.8 and 210.12 requirements where both apply, such as kitchen circuits).


Related Calculators

Calculator Use When...
Breaker Sizing Calculator Screening a standard breaker review point
Wire Size Calculator Determining conductor size for load
Ampacity Calculator Checking conductor ampacity after temperature or conductor-count adjustment
Residential Load Calculator Calculating total service load
Voltage Drop Calculator Checking wire length adequacy

After the Breaker Chart Lookup

Use the chart result as a screening point, not as the final project record. Before updating a panel schedule or selecting equipment, carry the same load basis through the Breaker Sizing Calculator and document the standard-size choice in the Breaker Size Chart. If conductor temperature rating, ambient temperature, or more than three current-carrying conductors changes the ampacity basis, review the NEC Ampacity Chart and run the adjusted value through the Ampacity Calculator before treating the breaker and conductor pair as coordinated. If the work changes an existing panel, update the Panel Load Schedule Chart so circuit identity, breaker poles, spare spaces, and panel limitations stay visible.

When the breaker serves equipment with an interrupting-rating or SCCR question, continue to the Short Circuit Calculator before treating the breaker selection as complete. Field installation still depends on the adopted NEC edition, listed equipment instructions, conductor terminal ratings, available fault current, and AHJ review.


Summary

Quick Reference Rules:

  • 14 AWG → 15A max (NEC 240.4(D))
  • 12 AWG → 20A max (NEC 240.4(D))
  • 10 AWG → 30A max (NEC 240.4(D))
  • Larger wire → Next standard size up allowed (NEC 240.4(B))
  • Continuous loads → 125% sizing (NEC 210.20(A))
  • Hot locations → Apply temperature correction
  • Multiple conductors → Apply fill derating

FAQ

What size wire do I need for a 30 amp breaker?

For a 30A breaker, use minimum 10 AWG copper wire (NEC 240.4(D)). For runs over 100 feet, consider upsizing to 8 AWG to account for voltage drop.

Can I use a 20 amp breaker on 14 gauge wire?

No. Per NEC 240.4(D), 14 AWG wire is limited to 15A overcurrent protection maximum. Using a 20A breaker would create a fire hazard.

What is the next size up rule?

NEC 240.4(B) allows using the next standard breaker size up when the conductor ampacity doesn't match a standard size (e.g., 55A ampacity → 60A breaker). This does NOT apply to 14, 12, and 10 AWG conductors.

Why does continuous load require 125% sizing?

Continuous loads (running 3+ hours) generate sustained heat in conductors and breakers. The 125% factor provides thermal margin to prevent nuisance tripping and extends equipment life.

How do I size a breaker for multiple loads?

Add all non-continuous loads at 100%, add all continuous loads at 125%, then select the next standard breaker size equal to or greater than the total.

Tags

NECbreaker sizingovercurrent protectioncircuit protection

Related Calculators

Need to Calculate Something?

Use our electrical calculators to solve your engineering problems quickly and accurately.