intermediateFeatured

NEC Ampacity Chart | 310.16 Wire Size Table

Use NEC ampacity chart/table 310.16: 12 AWG copper 20A, 10 AWG 30A, 4/0 copper 195A; compare 60C, 75C and 90C columns.

14 min read
Updated 6/7/2026
EleCalculator Team

Quick Answer: Use this page to confirm the base Table 310.16 ampacity and the terminal temperature column before you calculate anything else. Then move to the Wire Size Calculator when you need the actual conductor size for a known load and run, or to the Ampacity Calculator when ambient temperature, conductor count, or terminal limits must be combined into one answer.

Based on NEC 2023 (NFPA 70), Table 310.16. Applies to 0–2000 V conductors in raceway, ≤3 current-carrying conductors, 30°C (86°F) ambient. Reviewed 2026-06-07.

Quick Answer: Wire Size by Amperage

What wire size do I need? Use NEC Table 310.16. For most residential work, apply the 60°C column (limited by terminal ratings):

Wire Size Copper 60°C Copper 75°C Aluminum 75°C Common Use
14 AWG 15A 20A Lighting
12 AWG 20A 25A 20A Receptacles
10 AWG 30A 35A 30A Appliances
8 AWG 40A 50A 40A Ranges, A/C
6 AWG 55A 65A 50A Subpanels
4 AWG 70A 85A 65A Service
2 AWG 95A 115A 90A 100A service
1/0 AWG 125A 150A 120A 125A service
4/0 AWG 195A 230A 180A 200A service

Use the Wire Size Calculator for final conductor selection, and the Ampacity Calculator when temperature or conductor-count adjustments control the answer.


NEC Table 310.16 - Complete Reference

Copper Conductors - Insulated Conductors (0-2000V)

Based on ambient temperature of 30°C (86°F), not more than 3 current-carrying conductors in raceway:

AWG/kcmil 60°C (TW, UF) 75°C (THW, THWN) 90°C (THHN, XHHW)
18 14A
16 18A
14 15A 20A 25A
12 20A 25A 30A
10 30A 35A 40A
8 40A 50A 55A
6 55A 65A 75A
4 70A 85A 95A
3 85A 100A 115A
2 95A 115A 130A
1 110A 130A 145A
1/0 125A 150A 170A
2/0 145A 175A 195A
3/0 165A 200A 225A
4/0 195A 230A 260A
250 kcmil 215A 255A 290A
300 kcmil 240A 285A 320A
350 kcmil 260A 310A 350A
400 kcmil 280A 335A 380A
500 kcmil 320A 380A 430A

Aluminum Conductors - Insulated Conductors (0-2000V)

AWG/kcmil 60°C (TW, UF) 75°C (THW, THWN) 90°C (THHN, XHHW)
12 15A 20A 25A
10 25A 30A 35A
8 35A 40A 45A
6 40A 50A 55A
4 55A 65A 75A
3 65A 75A 85A
2 75A 90A 100A
1 85A 100A 115A
1/0 100A 120A 135A
2/0 115A 135A 150A
3/0 130A 155A 175A
4/0 150A 180A 205A
250 kcmil 170A 205A 230A
300 kcmil 190A 230A 260A
350 kcmil 210A 250A 280A
400 kcmil 225A 270A 305A
500 kcmil 260A 310A 350A

Understanding Temperature Ratings

Why Temperature Columns Matter

Column Insulation Types When to Use
60°C TW, UF Residential terminals (most common)
75°C THW, THWN, XHHW Commercial, industrial
90°C THHN, XHHW-2 Derating calculations only

Critical Rule: Use the LOWER of conductor insulation rating OR terminal rating.

Most residential equipment has 60°C terminals → Use 60°C column even with 90°C wire.

Terminal Temperature Limitations

Equipment Typical Terminal Rating
Residential panels 60°C or 75°C
Residential breakers 60°C or 75°C
Commercial equipment 75°C
Industrial equipment 75°C or 90°C

Wire Size for Specific Amperages

Quick Lookup: What Size Wire for... (Copper, 60°C)

Amperage Needed Minimum Wire Size Notes
15A 14 AWG Lighting circuits
20A 12 AWG Receptacles
30A 10 AWG Dryers, small A/C
40A 8 AWG Ranges, large A/C
50A 6 AWG Ranges, EV chargers
60A 4 AWG (55A) or 6 AWG 75°C Subpanels
70A 4 AWG Service
100A 2 AWG (95A) or 1 AWG 100A service
125A 1/0 AWG 125A service
150A 2/0 AWG (145A) or 3/0 AWG 150A service
200A 4/0 AWG (195A) or 250 kcmil 200A service

Quick Lookup: Aluminum Wire Sizes (75°C)

Amperage Aluminum Size Copper Equivalent
100A 1/0 AWG 2 AWG
125A 2/0 AWG (135A) 1/0 AWG
150A 3/0 AWG (155A) 2/0 AWG
200A 4/0 AWG (180A) 4/0 AWG

Residential Service Entrance Sizing

NEC 310.12 Service Conductor Sizing

Service Size Copper (60°C) Copper (75°C) Aluminum (75°C)
100A 2 AWG 3 AWG 1/0 AWG
125A 1/0 AWG 1 AWG 2/0 AWG
150A 3/0 AWG 2/0 AWG 3/0 AWG
200A 4/0 AWG 4/0 AWG 4/0 AWG
225A 250 kcmil 250 kcmil 250 kcmil
400A 500 kcmil 500 kcmil

Note: Service conductors may use 83% rule per NEC 310.12 for dwelling units.


Parallel Conductors

NEC 310.10(G) Parallel Conductor Requirements

When running conductors in parallel (1/0 AWG or larger):

Requirement Specification
Minimum size 1/0 AWG
Same length Required
Same material Required (all copper or all aluminum)
Same circular mil area Required
Same insulation type Required
Same termination method Required

Parallel Ampacity Calculation:

Total Ampacity = Single Conductor Ampacity × Number of Conductors

Example: Two 4/0 AWG copper THHN in parallel:

Total = 260A × 2 = 520A

Common Insulation Types

Insulation Type Reference

Type Temperature Description Common Use
TW 60°C Thermoplastic, wet General purpose, wet locations
THW 75°C Thermoplastic, heat-resistant, wet General purpose
THWN 75°C THW with nylon jacket Conduit, raceways
THHN 90°C Thermoplastic, high-heat, nylon Dry locations
XHHW 75°C wet, 90°C dry Cross-linked polyethylene Wet/dry locations
XHHW-2 90°C wet/dry Enhanced XHHW Industrial
USE 75°C Underground service entrance Direct burial
UF 60°C Underground feeder Direct burial

Worked Examples

Example 1: Residential 20A Circuit

Given: Kitchen receptacle circuit, 20A

Solution:

  1. Load: 20A
  2. Look up Table 310.16, 60°C column (residential terminals)
  3. Find: 12 AWG = 20A ✓

Answer: Use 12 AWG copper (minimum)

Example 2: 100A Subpanel

Given: Install 100A subpanel in detached garage

Solution:

  1. Load: 100A
  2. Table 310.16, 60°C: 2 AWG = 95A (too low)
  3. Table 310.16, 75°C: 3 AWG = 100A ✓
  4. Check terminal rating: If 75°C rated → 3 AWG OK
  5. If 60°C terminals → Use 1 AWG (110A)

Answer: Use 3 AWG copper (75°C terminals) or 1 AWG copper (60°C terminals)

Example 3: 200A Service with Aluminum

Given: 200A residential service, aluminum conductors

Solution:

  1. Load: 200A
  2. Table 310.16, Aluminum 75°C: 4/0 = 180A (close)
  3. Per NEC 310.12, dwelling services can use 83% rule
  4. 200A × 0.83 = 166A required
  5. 4/0 aluminum = 180A > 166A ✓

Answer: Use 4/0 AWG aluminum for 200A dwelling service

Example 4: Wire in Hot Attic

Given: 12 AWG THHN in 50°C (122°F) attic

Solution:

  1. Base ampacity (90°C): 30A
  2. Temperature correction factor (46-50°C): 0.82
  3. Corrected: 30A × 0.82 = 24.6A
  4. Terminal limitation (60°C): 20A maximum for 12 AWG

Answer: Maximum load is 20A (limited by terminal, not corrected ampacity)


Copper vs Aluminum Comparison

When to Use Each Material

Factor Copper Aluminum
Ampacity Higher per size ~78% of copper
Cost Higher Lower (larger size offsets)
Weight Heavier Lighter
Size for same ampacity Smaller 1-2 sizes larger
Terminations Standard Requires AL-rated devices
Common use Branch circuits Service entrance, feeders

Copper to Aluminum Equivalents

Copper Size Copper 75°C Aluminum Equivalent Aluminum 75°C
4 AWG 85A 2 AWG 90A
2 AWG 115A 1/0 AWG 120A
1/0 AWG 150A 3/0 AWG 155A
4/0 AWG 230A 250 kcmil 205A

Common Mistakes to Avoid

Mistake Why It's Wrong Correct Approach
Using 90°C ampacity at 60°C terminals Exceeds terminal rating Use terminal rating column
Ignoring aluminum requirements Improper termination Use AL-rated devices, anti-oxidant
Not checking terminal temperature May overload connections Verify breaker/equipment rating
Mixing copper and aluminum Galvanic corrosion Use proper bimetallic connectors

Related Calculators

Calculator Use When...
Wire Size Calculator Selecting conductor for load
Voltage Drop Calculator Long distance runs
Conduit Fill Calculator Determining conduit size
Breaker Sizing Calculator Matching wire to protection

Summary

Key Rules:

  • Use 60°C column for most residential (terminal limitation)
  • 14 AWG → 15A, 12 AWG → 20A, 10 AWG → 30A (fixed per NEC)
  • Aluminum is ~78% of copper ampacity (use 1-2 sizes larger)
  • Check terminal rating - limits usable ampacity
  • Service conductors may use 83% rule (NEC 310.12)

FAQ

What is wire ampacity?

Ampacity is the maximum current a conductor can carry continuously without exceeding its temperature rating. It's determined by conductor size, insulation type, installation conditions, and ambient temperature.

Why are there different temperature columns?

Different insulation types have different maximum operating temperatures. You must use the ampacity for the weakest point in the circuit - usually the terminal/connection temperature rating, not the wire's insulation rating.

Can I use aluminum wire for branch circuits?

Aluminum is generally not recommended for 15A and 20A branch circuits due to historical connection issues. It's commonly used for service entrance conductors and large feeders when properly terminated.

What size wire for 200 amp service?

For 200A residential service: 4/0 AWG copper (195A, uses 83% rule) or 4/0 AWG aluminum at 75°C. Verify local code requirements as some jurisdictions require larger sizing.

How do I account for ambient temperature?

Apply NEC Table 310.15(B)(1) correction factors to the base ampacity. Higher ambient temperatures reduce ampacity. Example: 90°C wire at 40°C ambient uses 0.91 factor.

What size wire for 30 amps?

Use 10 AWG copper (30A at 60°C per NEC Table 310.16). Typical 30A loads include electric dryers, water heaters, and small air conditioners. Always verify your equipment's terminal temperature rating before selecting the ampacity column.

What size wire for 50 amps?

Use 6 AWG copper at 60°C (55A, suitable for a 50A breaker) or 8 AWG copper at 75°C (exactly 50A). Typical 50A loads include electric ranges and Level 2 EV chargers. Confirm terminal ratings before applying the 75°C ampacity column.

Tags

NECampacityconductor sizingtemperature rating

Related Calculators

Need to Calculate Something?

Use our electrical calculators to solve your engineering problems quickly and accurately.