intermediateFeatured

NEC Ampacity Chart | Table 310.16 Wire Sizes

Use NEC 310.16 ampacity chart for copper/aluminum wire sizes, 60C/75C/90C columns, terminal limits, and 30A/50A handoffs.

14 min read
Updated 8/5/2026
EleCalculator Team

Quick Answer: Use this page as the NEC Table 310.16 reference for copper and aluminum base ampacity rows and temperature columns. Match the conductor material, insulation, and terminal rating first; then move to the Wire Size Calculator for load-to-conductor sizing or to the Ampacity Calculator when ambient temperature, conductor count, or terminal limits must be combined into one answer.

NFPA 70, the National Electrical Code, is the authoritative U.S. electrical installation document. Use the NEC edition adopted by the AHJ for the project, then verify equipment markings and manufacturer instructions before final conductor selection. Reviewed 2026-08-04.

How to use Table 310.16 without misapplying it

Table 310.16 is the base-ampacity reference. It is not the whole conductor-sizing answer. Use the table in this order before treating a row as a final project value:

  1. Define the load path: branch circuit, feeder, service, motor, HVAC, EVSE, listed equipment, or dwelling service.
  2. Choose conductor material, insulation type, and the terminal temperature rating that governs the installation.
  3. Record ambient temperature, current-carrying conductor count, raceway/bundling conditions, and whether voltage drop matters for the run.
  4. Use the Wire Size Calculator for load-to-conductor sizing or the Ampacity Calculator when derating factors must be combined.
  5. Return to Table 310.16 only after the calculator path identifies which conductor material and temperature column control.
Search task Inputs to enter first Calculator handoff
Wire size for a known load load current, continuous-duty status, material, terminal rating, distance Wire Size Calculator
Ampacity after derating base conductor, insulation rating, ambient temperature, conductor count, terminal limit Ampacity Calculator
Breaker and conductor coordination calculated load, conductor ampacity, standard OCPD size, small-conductor rules Breaker Sizing Calculator
Long feeder or branch-circuit run current, voltage, phase, conductor material, length, voltage-drop target Voltage Drop Calculator

NEC Table 310.16 Reference After the Calculator

Copper Conductors - Insulated Conductors (0-2000V)

Based on ambient temperature of 30°C (86°F), not more than 3 current-carrying conductors in raceway:

AWG/kcmil 60°C (TW, UF) 75°C (THW, THWN) 90°C (THHN, XHHW)
18 14A
16 18A
14 15A 20A 25A
12 20A 25A 30A
10 30A 35A 40A
8 40A 50A 55A
6 55A 65A 75A
4 70A 85A 95A
3 85A 100A 115A
2 95A 115A 130A
1 110A 130A 145A
1/0 125A 150A 170A
2/0 145A 175A 195A
3/0 165A 200A 225A
4/0 195A 230A 260A
250 kcmil 215A 255A 290A
300 kcmil 240A 285A 320A
350 kcmil 260A 310A 350A
400 kcmil 280A 335A 380A
500 kcmil 320A 380A 430A

Aluminum Conductors - Insulated Conductors (0-2000V)

AWG/kcmil 60°C (TW, UF) 75°C (THW, THWN) 90°C (THHN, XHHW)
12 15A 20A 25A
10 25A 30A 35A
8 35A 40A 45A
6 40A 50A 55A
4 55A 65A 75A
3 65A 75A 85A
2 75A 90A 100A
1 85A 100A 115A
1/0 100A 120A 135A
2/0 115A 135A 150A
3/0 130A 155A 175A
4/0 150A 180A 205A
250 kcmil 170A 205A 230A
300 kcmil 190A 230A 260A
350 kcmil 210A 250A 280A
400 kcmil 225A 270A 305A
500 kcmil 260A 310A 350A

Understanding Temperature Ratings

Why Temperature Columns Matter

Column Insulation Types When to Use
60°C TW, UF Residential terminals (most common)
75°C THW, THWN, XHHW Commercial, industrial
90°C THHN, XHHW-2 Derating calculations only

Critical Rule: Use the LOWER of conductor insulation rating OR terminal rating.

Most residential equipment has 60°C terminals → Use 60°C column even with 90°C wire.

Terminal Temperature Limitations

Equipment Typical Terminal Rating
Residential panels 60°C or 75°C
Residential breakers 60°C or 75°C
Commercial equipment 75°C
Industrial equipment 75°C or 90°C

Wire Size for Specific Amperages

Quick Lookup: What Size Wire for... (Copper, 60°C)

Amperage Needed Minimum Wire Size Notes
15A 14 AWG Lighting circuits
20A 12 AWG Receptacles
30A 10 AWG Dryers, small A/C
40A 8 AWG Ranges, large A/C
50A 6 AWG Ranges, EV chargers
60A 4 AWG (55A) or 6 AWG 75°C Subpanels
70A 4 AWG Service
100A 2 AWG (95A) or 1 AWG 100A service
125A 1/0 AWG 125A service
150A 2/0 AWG (145A) or 3/0 AWG 150A service
200A 4/0 AWG (195A) or 250 kcmil 200A service

Quick Lookup: Aluminum Wire Sizes (75°C)

Amperage Aluminum Size Copper Equivalent
100A 1/0 AWG 2 AWG
125A 2/0 AWG (135A) 1/0 AWG
150A 3/0 AWG (155A) 2/0 AWG
200A 4/0 AWG (180A) 4/0 AWG

Residential Service Entrance Sizing

NEC 310.12 Service Conductor Sizing

Service Size Copper (60°C) Copper (75°C) Aluminum (75°C)
100A 2 AWG 3 AWG 1/0 AWG
125A 1/0 AWG 1 AWG 2/0 AWG
150A 3/0 AWG 2/0 AWG 3/0 AWG
200A 4/0 AWG 4/0 AWG 4/0 AWG
225A 250 kcmil 250 kcmil 250 kcmil
400A 500 kcmil 500 kcmil

Note: Service conductors may use 83% rule per NEC 310.12 for dwelling units.


Parallel Conductors

NEC 310.10(G) Parallel Conductor Requirements

When running conductors in parallel (1/0 AWG or larger):

Requirement Specification
Minimum size 1/0 AWG
Same length Required
Same material Required (all copper or all aluminum)
Same circular mil area Required
Same insulation type Required
Same termination method Required

Parallel Ampacity Calculation:

Total Ampacity = Single Conductor Ampacity × Number of Conductors

Example: Two 4/0 AWG copper THHN in parallel:

Total = 260A × 2 = 520A

Common Insulation Types

Insulation Type Reference

Type Temperature Description Common Use
TW 60°C Thermoplastic, wet General purpose, wet locations
THW 75°C Thermoplastic, heat-resistant, wet General purpose
THWN 75°C THW with nylon jacket Conduit, raceways
THHN 90°C Thermoplastic, high-heat, nylon Dry locations
XHHW 75°C wet, 90°C dry Cross-linked polyethylene Wet/dry locations
XHHW-2 90°C wet/dry Enhanced XHHW Industrial
USE 75°C Underground service entrance Direct burial
UF 60°C Underground feeder Direct burial

Calculator Checks Instead of Static Answers

Use these scenarios as input prompts for the calculators rather than as standalone answers. The correct conductor depends on the adopted code path, terminal markings, insulation type, ambient temperature, conductor count, and voltage-drop needs.

Branch-circuit conductor check

Before using the table, collect:

  • load current and continuous-duty status
  • conductor material and insulation type
  • equipment terminal temperature rating
  • ambient temperature and conductor-count adjustment
  • voltage-drop run length, if the run is long

Enter those values in the Wire Size Calculator, then compare the resulting conductor path with the Table 310.16 reference below.

Feeder or subpanel conductor check

Before selecting a feeder conductor, collect:

  • feeder calculated load
  • service voltage and phase
  • copper or aluminum basis
  • terminal rating at both ends
  • raceway/bundling and ambient conditions
  • voltage-drop target for the route

Use the Ampacity Calculator when derating controls, and use the Voltage Drop Calculator when the distance controls.

Dwelling service conductor check

A dwelling service question needs the adopted NEC edition, utility/AHJ requirements, service size basis, conductor material, terminal markings, and any local worksheet requirement. Use the residential service and wire-size calculators first; use Table 310.16 only after the applicable dwelling-service rule is known.

Hot attic or derated conductor check

For high ambient temperature, rooftop exposure, or multiple current-carrying conductors, do not copy a base table value. Enter the insulation rating, base conductor, ambient temperature, conductor count, terminal rating, and rooftop/bundling condition in the Ampacity Calculator, then compare the adjusted result with the terminal limit.


Copper vs Aluminum Comparison

When to Use Each Material

Factor Copper Aluminum
Ampacity Higher per size ~78% of copper
Cost Higher Lower (larger size offsets)
Weight Heavier Lighter
Size for same ampacity Smaller 1-2 sizes larger
Terminations Standard Requires AL-rated devices
Common use Branch circuits Service entrance, feeders

Copper to Aluminum Equivalents

Copper Size Copper 75°C Aluminum Equivalent Aluminum 75°C
4 AWG 85A 2 AWG 90A
2 AWG 115A 1/0 AWG 120A
1/0 AWG 150A 3/0 AWG 155A
4/0 AWG 230A 250 kcmil 205A

Common Mistakes to Avoid

Mistake Why It's Wrong Correct Approach
Using 90°C ampacity at 60°C terminals Exceeds terminal rating Use terminal rating column
Ignoring aluminum requirements Improper termination Use AL-rated devices, anti-oxidant
Not checking terminal temperature May overload connections Verify breaker/equipment rating
Mixing copper and aluminum Galvanic corrosion Use proper bimetallic connectors

Related Calculators

Calculator Use When...
Wire Size Calculator Selecting conductor for load
Voltage Drop Calculator Long distance runs
Conduit Fill Calculator Determining conduit size
Breaker Sizing Calculator Matching wire to protection

Summary

Key Rules:

  • Use 60°C column for most residential (terminal limitation)
  • Small-conductor limits still need the applicable NEC path before a table row becomes a final breaker or conductor answer
  • Aluminum is ~78% of copper ampacity (use 1-2 sizes larger)
  • Check terminal rating - limits usable ampacity
  • Service conductors may use 83% rule (NEC 310.12)

FAQ

What is wire ampacity?

Ampacity is the maximum current a conductor can carry continuously without exceeding its temperature rating. It's determined by conductor size, insulation type, installation conditions, and ambient temperature.

Why are there different temperature columns?

Different insulation types have different maximum operating temperatures. You must use the ampacity for the weakest point in the circuit - usually the terminal/connection temperature rating, not the wire's insulation rating.

Can I use aluminum wire for branch circuits?

Aluminum is generally not recommended for 15A and 20A branch circuits due to historical connection issues. It's commonly used for service entrance conductors and large feeders when properly terminated.

What size wire for 200 amp service?

Enter the service size, dwelling-service basis, conductor material, terminal markings, ambient conditions, and local code path in the calculator workflow. Then compare the selected path with the adopted NEC edition, utility requirements, and AHJ worksheet.

How do I account for ambient temperature?

Apply NEC temperature correction factors to the base ampacity selected from the correct insulation column, then compare the adjusted value with the governing terminal limit. Use the ampacity calculator when temperature and conductor-count adjustments both apply.

What size wire for 30 amps?

Use the wire-size calculator with load current, duty cycle, conductor material, terminal rating, ambient temperature, conductor count, and run length. After the calculator identifies the governing path, use Table 310.16 as the reference for the base ampacity column.

What size wire for 50 amps?

Enter the equipment type, continuous-load status, terminal rating, conductor material, installation conditions, and voltage-drop needs before selecting a conductor. Then verify the Table 310.16 row, OCPD coordination, and equipment listing together.

Tags

NECampacityconductor sizingtemperature rating

Related Calculators

Frequently Asked Questions

What size wire for 200 amp service?
Enter the service size, conductor material, terminal temperature rating, dwelling-service basis, ambient conditions, conductor count, and local code path in the wire-size workflow. Table 310.16 and any dwelling-service rule only make sense after those inputs are known, and the AHJ may require a different adopted-edition worksheet.
What size wire for 100 amp service?
Treat this as a service or feeder sizing workflow, not a standalone table lookup. Use the calculator with load current, conductor material, terminal rating, voltage drop, installation conditions, and the adopted NEC path before comparing any Table 310.16 row.
What size wire for 30 amps?
Use the wire-size calculator with load current, continuous-duty status, conductor material, insulation, terminal rating, ambient temperature, conductor count, and voltage-drop run length. Then use Table 310.16 as the base-ampacity reference rather than copying one row from a chart.
What size wire for 50 amps?
Start with the actual load and equipment markings. EVSE, ranges, welders, feeders, and other equipment can have different continuous-load, terminal, and listing requirements, so enter the installation details before choosing a conductor from the reference table.
What is the difference between the 60°C, 75°C, and 90°C ampacity columns?
The columns correspond to insulation temperature ratings. Always use the column matching the lowest-rated component — most residential breakers and outlets are 60°C-rated, so use the 60°C column even with 90°C-rated THHN wire. The 90°C column is used only for derating calculations.
Can I use aluminum wire for a 200A residential service?
Aluminum is common for services and feeders when the conductors, lugs, torque, compound, and equipment markings are suitable for aluminum. Confirm the adopted NEC edition, dwelling-service path, utility requirements, and AHJ worksheet before treating any table row as the final service-conductor answer.

Need to Calculate Something?

Use our electrical calculators to solve your engineering problems quickly and accurately.