Motors & Loads calculator
Full Load Current Calculator
Use this full load current calculator when the job is an NEC Table 430.248/430.250 motor FLC lookup. Enter motor HP, voltage, and phase count to get the exact NEC table value, minimum conductor ampacity (125% per NEC 430.22), overload-basis reminder, and maximum branch-circuit breaker screen (250% per NEC 430.52 for inverse-time breakers). Common field lookups land here directly: 10 HP at 460V is 14A, 50 HP at 460V is 65A, and 200 HP at 460V is 240A.
Updated June 21, 2026
NEC Table 430.250 lists 14A for a 10 HP, 460V, 3-phase motor and 240A for a 200 HP, 460V, 3-phase motor. Use these table FLC values for conductor and branch-circuit fault-protection screens, not overload settings.
200 HP @ 460V = 240A table FLC | 125% conductor screen = 300A | 250% inverse-time breaker screen = 600A
Enter HP, voltage, and phase count below to look up NEC table FLC before conductor, branch-protection, or nameplate-overload review
Calculator Inputs
Calculation Results
Enter values above to see calculation results
Field kit
Tools for FLC checks
Use the table current as a sizing reference, then compare field tools for measured current and nameplate documentation.
As an Amazon Associate I earn from qualifying purchases.
Calculation history
Example Calculations
10 HP Motor at 460V Three-Phase
NEC Table 430.250: 10 HP at 460V = 14A FLC. Conductor: 14A × 125% = 17.5A min. Breaker: 14A × 250% = 35A max.
- Motor HP: 10
- Voltage: 460 V
- Phases: Three phase
50 HP Motor at 230V Three-Phase
NEC Table 430.250: 50 HP at 230V = 130A FLC. Conductor: 130A × 125% = 162.5A min. Breaker: 130A × 250% = 325A max.
- Motor HP: 50
- Voltage: 230 V
- Phases: Three phase
How to Use
Full Load Current (FLC) Calculator — NEC Article 430
This calculator performs an instant lookup of motor full load current from NEC Table 430.248 (single-phase) and NEC Table 430.250 (three-phase). Per NEC 430.6(A)(1), these table values — not motor nameplate FLA — must be used for sizing conductors and branch-circuit protection devices.
How to Use This Calculator
- Enter Motor HP — Standard NEMA motor sizes: 1, 1.5, 2, 3, 5, 7.5, 10, 15, 20, 25, 30, 40, 50, 60, 75, 100, 125, 150, 200 HP
- Select System Voltage — 115V, 200V, 208V, 230V, 460V, or 575V
- Select Phase Count — Single-phase (NEC 430.248) or three-phase (NEC 430.250)
What the Results Mean
- NEC Table FLC — The exact full load current from the NEC table for your motor HP and voltage. Use this for conductor sizing and breaker selection.
- Min Conductor Ampacity — FLC × 125% per NEC 430.22. This is the minimum ampacity your branch-circuit conductors must have.
- Overload Protection Basis — Use actual motor nameplate FLA per NEC 430.32. Do not calculate the overload setting from table FLC.
- Max Branch-Circuit Breaker — FLC × 250% for inverse time circuit breakers per NEC 430.52 Table 430.52(C)(1).
NEC Table 430.250 Quick Reference — 460V Three-Phase
| Motor HP | FLC (A) | Min Conductor (125%) | Max Breaker (250%) |
|---|---|---|---|
| 5 | 7.6 | 9.5 A | 19 A |
| 10 | 14 | 17.5 A | 35 A |
| 25 | 34 | 42.5 A | 85 A |
| 50 | 65 | 81.3 A | 163 A |
| 100 | 124 | 155 A | 310 A |
| 200 | 240 | 300 A | 600 A |
NEC Table 430.250 200 HP 460V full load current
For the direct lookup, 200 HP at 460V three-phase is 240 A in NEC Table 430.250. The minimum conductor ampacity screen is 300 A, and the inverse-time breaker screen is 600 A before final device selection, conductor derating, terminal limits, voltage drop, and equipment instructions are reviewed.
FLC vs FLA — The Critical NEC Distinction
NEC Article 430 requires using two different current values for different purposes:
- Table FLC (Full Load Current) — From NEC Tables 430.248/430.250 → Used for conductor sizing (430.22), branch-circuit protection (430.52), and disconnect sizing.
- Nameplate FLA (Full Load Amps) — From motor nameplate → Used exclusively for overload protection sizing (430.32).
Mixing these values is a common code violation. The NEC table values are intentionally conservative to account for motor manufacturing variations across brands.
NEC 430 Key Sections Reference
- 430.6(A)(1) — Mandates use of Table 430.248/430.250 values (not nameplate) for conductor and protection sizing
- 430.22 — Conductor ampacity ≥ 125% of motor FLC for continuous duty
- 430.32 — Overload protection: commonly 125% of nameplate FLA when service factor is ≥1.15 or temperature rise is 40°C or less; otherwise 115% of nameplate FLA
- 430.52 — Branch-circuit short-circuit protection: 250% max for inverse time breaker, 175% for dual-element fuse
- 430.110 — Disconnect: 115% of motor FLC
Next Steps After the FLC Lookup
After the table value is confirmed, use the Motor Cable Size Calculator to keep voltage drop, terminal limits, and conductor ampacity together. For short-circuit and ground-fault device sizing, continue with the Motor Branch Protection Calculator.
Common Applications
Motor branch-circuit conductor sizing
Breaker and fuse selection for motor circuits
Overload relay sizing and coordination
Electrical permit load calculations
Motor control center (MCC) design
Industrial facility electrical design
Frequently Asked Questions
What is full load current (FLC) and how is it different from full load amps (FLA)?
How do I size a breaker for a motor using NEC 430.52?
Why does NEC use table values instead of nameplate current for conductor sizing?
What is the 125% rule in NEC 430.22 for motor conductors?
Related Calculators
Motor Cable Size Calculator
Screen NEC table motor conductor size with ampacity derating, termination limits, and branch-circuit voltage drop.
ExploreMotor Power
Open the motor power for related motors & loads review.
ExploreMotor Starting Current Calculator
Compare induction-motor DOL, star-delta, soft-starter, VFD, and autotransformer starting current screens.
ExploreAmpacity Calculator
Individual conductor ampacity and derating per NEC 310.16 with ambient-temperature correction, current-carrying conductor adjustment, and terminal-rating limits.
ExploreWire Size Calculator
Handle conductor gauge selection from load current, standard OCPD, and voltage drop after ampacity and raceway constraints are known.
ExploreCircuit Breaker Sizing Calculator
NEC-oriented standard breaker review-point screen with simplified conductor protection checks.
Explore