Motors & Loads calculator

Full Load Current Calculator

Use this full load current calculator when the job is an NEC Table 430.248/430.250 motor FLC lookup. Enter motor HP, voltage, and phase count to get the exact NEC table value, minimum conductor ampacity (125% per NEC 430.22), overload-basis reminder, and maximum branch-circuit breaker screen (250% per NEC 430.52 for inverse-time breakers). Common field lookups land here directly: 10 HP at 460V is 14A, 50 HP at 460V is 65A, and 200 HP at 460V is 240A.

Updated June 21, 2026

NEC Table 430.250 lists 14A for a 10 HP, 460V, 3-phase motor and 240A for a 200 HP, 460V, 3-phase motor. Use these table FLC values for conductor and branch-circuit fault-protection screens, not overload settings.

200 HP @ 460V = 240A table FLC | 125% conductor screen = 300A | 250% inverse-time breaker screen = 600A

Enter HP, voltage, and phase count below to look up NEC table FLC before conductor, branch-protection, or nameplate-overload review

Calculator Inputs

Quick Presets

Motor rated horsepower (HP). Common sizes: 1, 1.5, 2, 3, 5, 7.5, 10, 15, 20, 25, 30, 40, 50, 60, 75, 100, 125, 150, 200 HP

System voltage. NEC tables cover standard voltage ranges.

Single-phase uses NEC Table 430.248, three-phase uses NEC Table 430.250

Calculation Results

Enter values above to see calculation results

Field kit

Tools for FLC checks

Use the table current as a sizing reference, then compare field tools for measured current and nameplate documentation.

As an Amazon Associate I earn from qualifying purchases.

Opens in a new tabOpens in a new tabOpens in a new tab
Calculation history

Example Calculations

10 HP Motor at 460V Three-Phase

NEC Table 430.250: 10 HP at 460V = 14A FLC. Conductor: 14A × 125% = 17.5A min. Breaker: 14A × 250% = 35A max.

Inputs
  • Motor HP: 10
  • Voltage: 460 V
  • Phases: Three phase

50 HP Motor at 230V Three-Phase

NEC Table 430.250: 50 HP at 230V = 130A FLC. Conductor: 130A × 125% = 162.5A min. Breaker: 130A × 250% = 325A max.

Inputs
  • Motor HP: 50
  • Voltage: 230 V
  • Phases: Three phase

How to Use

Full Load Current (FLC) Calculator — NEC Article 430

This calculator performs an instant lookup of motor full load current from NEC Table 430.248 (single-phase) and NEC Table 430.250 (three-phase). Per NEC 430.6(A)(1), these table values — not motor nameplate FLA — must be used for sizing conductors and branch-circuit protection devices.

How to Use This Calculator

  1. Enter Motor HP — Standard NEMA motor sizes: 1, 1.5, 2, 3, 5, 7.5, 10, 15, 20, 25, 30, 40, 50, 60, 75, 100, 125, 150, 200 HP
  2. Select System Voltage — 115V, 200V, 208V, 230V, 460V, or 575V
  3. Select Phase Count — Single-phase (NEC 430.248) or three-phase (NEC 430.250)

What the Results Mean

  • NEC Table FLC — The exact full load current from the NEC table for your motor HP and voltage. Use this for conductor sizing and breaker selection.
  • Min Conductor Ampacity — FLC × 125% per NEC 430.22. This is the minimum ampacity your branch-circuit conductors must have.
  • Overload Protection Basis — Use actual motor nameplate FLA per NEC 430.32. Do not calculate the overload setting from table FLC.
  • Max Branch-Circuit Breaker — FLC × 250% for inverse time circuit breakers per NEC 430.52 Table 430.52(C)(1).

NEC Table 430.250 Quick Reference — 460V Three-Phase

Motor HP FLC (A) Min Conductor (125%) Max Breaker (250%)
57.69.5 A19 A
101417.5 A35 A
253442.5 A85 A
506581.3 A163 A
100124155 A310 A
200240300 A600 A

NEC Table 430.250 200 HP 460V full load current

For the direct lookup, 200 HP at 460V three-phase is 240 A in NEC Table 430.250. The minimum conductor ampacity screen is 300 A, and the inverse-time breaker screen is 600 A before final device selection, conductor derating, terminal limits, voltage drop, and equipment instructions are reviewed.

FLC vs FLA — The Critical NEC Distinction

NEC Article 430 requires using two different current values for different purposes:

  • Table FLC (Full Load Current) — From NEC Tables 430.248/430.250 → Used for conductor sizing (430.22), branch-circuit protection (430.52), and disconnect sizing.
  • Nameplate FLA (Full Load Amps) — From motor nameplate → Used exclusively for overload protection sizing (430.32).

Mixing these values is a common code violation. The NEC table values are intentionally conservative to account for motor manufacturing variations across brands.

NEC 430 Key Sections Reference

  • 430.6(A)(1) — Mandates use of Table 430.248/430.250 values (not nameplate) for conductor and protection sizing
  • 430.22 — Conductor ampacity ≥ 125% of motor FLC for continuous duty
  • 430.32 — Overload protection: commonly 125% of nameplate FLA when service factor is ≥1.15 or temperature rise is 40°C or less; otherwise 115% of nameplate FLA
  • 430.52 — Branch-circuit short-circuit protection: 250% max for inverse time breaker, 175% for dual-element fuse
  • 430.110 — Disconnect: 115% of motor FLC

Next Steps After the FLC Lookup

After the table value is confirmed, use the Motor Cable Size Calculator to keep voltage drop, terminal limits, and conductor ampacity together. For short-circuit and ground-fault device sizing, continue with the Motor Branch Protection Calculator.

Common Applications

Motor branch-circuit conductor sizing

Breaker and fuse selection for motor circuits

Overload relay sizing and coordination

Electrical permit load calculations

Motor control center (MCC) design

Industrial facility electrical design

Frequently Asked Questions

What is full load current (FLC) and how is it different from full load amps (FLA)?
Full Load Current (FLC) is the standardized current from NEC Tables 430.248/430.250 used for conductor sizing and protection device selection. Full Load Amps (FLA) is the actual current on the motor nameplate. NEC requires using table FLC for conductor sizing (430.22) and branch-circuit protection (430.52), but nameplate FLA for overload protection (430.32). Example: A 10 HP, 460V three-phase motor has table FLC of 14A, but nameplate FLA might be 12.8A or 14.2A depending on manufacturer.
How do I size a breaker for a motor using NEC 430.52?
Per NEC 430.52 and Table 430.52(C)(1): For inverse time circuit breakers, the maximum rating is 250% of motor FLC from NEC Table 430.250. For dual-element time-delay fuses, maximum is 175% of FLC. Example: 50 HP motor at 460V has FLC of 65A. Maximum inverse time breaker: 65A × 250% = 162.5A → next standard size 175A. Maximum dual-element fuse: 65A × 175% = 113.75A → next standard size 110A.
Why does NEC use table values instead of nameplate current for conductor sizing?
NEC uses standardized table values because different manufacturers produce motors with varying nameplate currents for the same HP rating. Using table values ensures conductors are sized consistently regardless of which motor is eventually installed. This provides flexibility for motor replacement without rewiring. The table values are intentionally conservative to accommodate manufacturing variations across the industry.
What is the 125% rule in NEC 430.22 for motor conductors?
NEC 430.22 requires branch-circuit conductors supplying a single continuous-duty motor to have an ampacity not less than 125% of the motor FLC from NEC tables. This accounts for motor heating characteristics, starting current effects, and ensures conductor longevity. Example: 10 HP at 460V = 14A FLC × 125% = 17.5A minimum conductor ampacity. Select 12 AWG copper (25A at 75°C) or larger.