Service Loads & Motors calculator
Full Load Current Calculator
Enter motor HP, voltage, and phase to look up the NEC Table 430.248 or 430.250 full-load current. The calculator returns the selected table value for conductor and branch-protection review, keeps nameplate FLA separate for overload settings, and points the result into the next motor-circuit planning step.
Updated August 5, 2026
Enter motor HP, voltage, and phase to look up NEC Table 430.248/430.250 FLC, then use table FLC for conductor and branch-protection screens but not overload settings.
NEC table method: select HP -> select voltage -> select phase -> review conductor and branch-protection context from the calculated row
Enter HP, voltage, and phase below to confirm NEC table FLC before conductor, branch-protection, or nameplate-overload review
Source: NFPA 70, National Electrical CodeOpens in a new tab | Last reviewed: 2026-08-04
Final installation decisions must use the adopted NEC edition, equipment listings, and AHJ requirements.
Calculator Inputs
Calculation Results
Enter values above to see calculation results
Field kit
Tools for FLC checks
Use the table current as a sizing reference, then compare field tools for measured current and nameplate documentation.
As an Amazon Associate I earn from qualifying purchases.
Calculation history
Example Calculations
More examples. Open to review 2 additional calculation examples.
How to Use
Motor FLC Calculator - NEC 430.248 and 430.250
Enter motor HP, voltage, and phase to look up NEC Table 430.248 or 430.250. In the Article 430 workflow, these table values are used for conductor and branch-circuit protection review, while motor nameplate FLA remains the overload basis.
How to Use This Calculator
- Enter Motor HP — Standard NEMA motor sizes: 1, 1.5, 2, 3, 5, 7.5, 10, 15, 20, 25, 30, 40, 50, 60, 75, 100, 125, 150, 200 HP
- Select System Voltage — 115V, 200V, 208V, 230V, 460V, or 575V
- Select Phase Count — Single-phase (NEC 430.248) or three-phase (NEC 430.250)
What the Results Mean
- NEC Table FLC — The table full-load current for the selected motor HP and voltage. Use this as the conductor and branch-protection review basis before equipment and AHJ checks.
- Min Conductor Ampacity — FLC × 125% per NEC 430.22. This is the minimum ampacity your branch-circuit conductors must have.
- Overload Protection Basis — Use actual motor nameplate FLA per NEC 430.32. Do not calculate the overload setting from table FLC.
- Max Branch-Circuit Breaker — FLC × 250% for inverse time circuit breakers per NEC 430.52 Table 430.52(C)(1).
NEC Table 430.250 reference and result handoff
Use the selected HP, voltage, and phase count before carrying table FLC into conductor ampacity, branch-circuit short-circuit and ground-fault protection, disconnect, and documentation review. The result should stay tied to the motor entered on this page.
Use the lookup result in the next review
After the calculator returns the table FLC for your selected motor, continue into conductor ampacity, branch-circuit protection, terminal rating, derating, voltage-drop, and equipment-instruction review. Keep the nameplate FLA separate for overload settings.
FLC vs FLA — The Critical NEC Distinction
NEC Article 430 motor review uses different current values for different purposes:
- Table FLC (Full Load Current) — From NEC Tables 430.248/430.250 → Used for conductor sizing (430.22), branch-circuit protection (430.52), and disconnect sizing.
- Nameplate FLA (Full Load Amps) — From motor nameplate → Used exclusively for overload protection sizing (430.32).
Mixing these values is a common review error. The NEC table values are intentionally conservative to account for motor manufacturing variations across brands.
NEC 430 Key Sections Reference
- 430.6(A)(1) — Points conductor and branch-protection sizing toward Table 430.248/430.250 values for the motor types covered here
- 430.22 — Conductor ampacity ≥ 125% of motor FLC for continuous duty
- 430.32 — Overload protection: commonly 125% of nameplate FLA when service factor is ≥1.15 or temperature rise is 40°C or less; otherwise 115% of nameplate FLA
- 430.52 — Branch-circuit short-circuit protection: 250% max for inverse time breaker, 175% for dual-element fuse
- 430.110 — Disconnect: 115% of motor FLC
Next Steps After the FLC Lookup
After the table value is confirmed, use the Motor Cable Size Calculator to keep voltage drop, terminal limits, and conductor ampacity together. For short-circuit and ground-fault device sizing, continue with the Motor Branch Protection Calculator.
Common Applications
More applications. Open to review 3 additional use cases.
Frequently Asked Questions
What is full load current (FLC) and how is it different from full load amps (FLA)?
How do I size a breaker for a motor using NEC 430.52?
Why does NEC use table values instead of nameplate current for conductor sizing?
What is the 125% rule in NEC 430.22 for motor conductors?
Related Calculators
Screen NEC table motor conductor size with ampacity derating, termination limits, and branch-circuit voltage drop.
Open the motor power for related service loads & motors review.
Compare induction-motor DOL, star-delta, soft-starter, VFD, and autotransformer starting current screens.
Individual conductor ampacity and derating per NEC 310.16 with ambient-temperature correction, current-carrying conductor adjustment, and terminal-rating limits.
Handle conductor gauge selection from load current, standard OCPD, and voltage drop after ampacity and raceway constraints are known.
NEC-oriented standard breaker review-point screen with simplified conductor protection checks.