Motors & Loads calculator

Motor Cable Sizing Calculator

Use this calculator-led motor cable sizing screen by entering motor HP, voltage, phase count, conductor material, insulation type, termination rating, ambient factor, conductor count, one-way run length, and voltage-drop target. The page keeps NEC table FLC, NEC 430.22 conductor ampacity, termination limits, derating, and voltage drop in the calculator output instead of treating one sample motor as the answer for every motor cable query.

Updated July 10, 2026

Enter HP, voltage, phase, conductor material, insulation, termination rating, ambient factor, conductor count, and run length to screen NEC table FLC, conductor ampacity, and voltage drop.

Method path: table FLC lookup -> 125% conductor screen -> derating and termination check -> voltage-drop review.

Enter motor size, voltage, phase count, conductor data, and run length below to screen branch-circuit wire size and voltage drop

Calculator Inputs

Field notes

Calculation Results

Enter values above to see calculation results

Opens in a new tabOpens in a new tabOpens in a new tab
Calculation history

Example Calculations

Use this preset: standard branch-circuit runLoad a common motor branch-circuit scenario, then let the calculator output compare table FLC, conductor ampacity, terminations, and voltage drop.InputsMotor Power: 10Power Unit: HpVoltage: 460 VPhases: Three phaseConductor Material: CopperInsulation Type: THHN/THWN-2Termination Rating: 75Ambient Temperature: 30Current Carrying Conductors: 3One Way Length: 100Voltage Drop Limit: 3
Use this preset: longer run with derating pressureLoad a longer-run scenario, then review how the calculator output separates ampacity, derating, termination rating, and voltage-drop pressure.InputsMotor Power: 50Power Unit: HpVoltage: 460 VPhases: Three phaseConductor Material: CopperInsulation Type: THHN/THWN-2Termination Rating: 75Ambient Temperature: 45Current Carrying Conductors: 4One Way Length: 350Voltage Drop Limit: 3

How to Use

Motor Cable Sizing for NEC Article 430 Planning

This page is built for the search intent behind queries such as motor cable size calculator, motor wire size calculator, and 3 phase motor cable size calculator. The key idea is simple: motor conductor sizing starts with NEC table full-load current, not with a generic power formula or a nameplate overload setting.

What the Calculator Actually Does

  • Looks up NEC table FLC from horsepower, voltage, and phase count.
  • Applies NEC 430.22 by screening conductor ampacity at 125% of table FLC for one motor branch circuits.
  • Checks the selected termination basis so a 60°C or 75°C equipment limit can cap the usable ampacity.
  • Reviews branch-circuit voltage drop using the entered one-way length and the NEC table running current.

Why the Calculator Uses Table FLC Instead of Motor Nameplate Current

NEC 430.6(A)(1) sends branch-circuit conductor sizing back to the standard ampere ratings in the NEC motor tables. For the AC motors modeled here, that means Table 430.248 for single-phase motors and Table 430.250 for three-phase motors. This is different from overload protection, which follows actual motor nameplate current under NEC 430.32.

Current Basis Typical Job Used on This Page?
NEC Table FLC Branch-circuit conductor sizing under NEC 430.6(A)(1) and 430.22 Yes
Motor Nameplate FLA Motor overload-device settings under NEC 430.32 No
Formula Current General load comparison and engineering review No

Method reference after using the calculator

Use the calculator above for the actual motor HP, voltage, phase count, conductor material, insulation type, termination rating, ambient factor, conductor count, and run length. The reference below explains the method after you have a calculator output for the specific motor circuit.

Core Formula Used by the Conductor Screen

Minimum Motor Branch-Circuit Conductor Ampacity = NEC Table FLC × 1.25

That is the basic single-motor rule from NEC 430.22. This page then checks whether the selected conductor still clears that ampacity after the entered ambient-temperature and conductor-count adjustments, and whether the selected 60°C or 75°C termination column still permits the result.

Preset examples

Use the presets above to compare a standard branch-circuit run and a longer run with derating pressure. Enter the actual motor data, conductor details, termination basis, ambient condition, conductor count, and run length before carrying the calculator output to conductor schedules or downstream protection tools.

Why Termination Rating Still Matters on 90°C Insulation

Many field installations use 90°C insulation such as THHN/THWN-2 or XHHW-2. That higher column is often used as the starting point for ambient and conductor-count adjustments, but the final usable ampacity can still be limited by a 60°C or 75°C equipment termination basis. This page keeps that distinction visible so the result does not overstate usable ampacity.

How Voltage Drop Is Treated Here

Voltage drop is shown as a design screen. It is not presented as a blanket code pass/fail rule for every case, but many designers and installers still target about 3% on the branch circuit to keep motor starting and running performance from drifting too far. The calculator only uses running current for this check, so very long runs and difficult starts may still need a deeper review.

What This Page Does Not Claim

This page does not claim to model every motor conductor problem. It does not replace the adopted NEC edition, actual equipment lugs, field ampacity adjustments beyond the entered data, or manufacturer guidance for adjustable-speed drives and specialty motor installations. It is an honest branch-circuit wire-size screen for common AC motor work.

Common Applications

Preliminary branch-circuit wire sizing for one AC motor
Three-phase and single-phase conductor screening from NEC table full-load current
Comparing copper and aluminum options on the same motor circuit
More applications. Open to review 3 additional use cases.
Checking whether ambient temperature or conductor count forces upsizing
Reviewing branch-circuit voltage drop on longer motor runs
Fast reference for common 230V, 460V, and 575V motor conductor questions

Frequently Asked Questions

How do I size wire for a motor under NEC Article 430?
For a standard one-motor branch circuit, the usual starting point is NEC table full-load current multiplied by 125% under NEC 430.22. After that, the conductor still has to clear any applicable ambient-temperature and conductor-count adjustments, and the final usable ampacity can still be limited by the equipment termination column.
Why does the calculator use NEC table FLC instead of motor nameplate amps?
Because NEC 430.6(A)(1) sends branch-circuit conductor sizing to the standard motor-table current values. Motor nameplate current is important for overload-device settings, but it is not the normal branch-circuit conductor-sizing basis for the AC motor work screened on this page.
Does 90°C insulation mean I can always use the 90°C ampacity as my final wire size?
No. The 90°C column may be the starting point for derating, but the final usable ampacity can still be capped by a 60°C or 75°C equipment termination basis. That is why this calculator keeps the termination limit visible in the result.
What if the voltage-drop target pushes the wire larger than the ampacity-only size?
Then the larger conductor is the better branch-circuit recommendation for that design target. This is common on longer runs where the first ampacity-compliant size is electrically safe but still drops more voltage than the project wants to allow.
Can I use this page for every VFD output cable and specialty motor installation?
No. This page is intentionally narrower than that. Adjustable-speed drive output conductors, harmonic-rich installations, and specialty motor circuits may need a separate review using the drive manufacturer documentation and the exact code rules that apply to that installation.

Related Calculators

Browse all calculators