intermediateFeatured

3-Phase Formula Guide | kW, Amps & kVA

Use three-phase formulas for kW, amps, kVA, line voltage, current, power factor, and wye/delta inputs before calculator checks.

14 min read
Updated 8/5/2026
EleCalculator Team

Quick Answer

What are the key three-phase formulas to choose before calculating?

Calculate Formula
Power (kW) P = √3 × V_L × I_L × PF ÷ 1000
Current (A) I = P × 1000 ÷ (√3 × V × PF)
Apparent Power (kVA) S = √3 × V_L × I_L ÷ 1000

Where √3 = 1.732

Choose the known values first, then use the 3-Phase Calculator or the related tools below for the actual voltage, current, kW, kVA, and power-factor inputs.


After the Formula Result

Use the formula result as the first calculation, then close the workflow with the right calculator handoff:

If the result is... Next check
A motor running-current estimate Compare against the Motor Current Calculator and nameplate data
A service or feeder load in kVA Review current and transformer relationships with the Transformer Calculator
A long circuit run Check the same current in the Voltage Drop Calculator
A low power factor load Continue with the Power Factor Calculator before sizing correction equipment

For code-sensitive conductor, breaker, or equipment decisions, verify the adopted NEC edition, equipment listings, manufacturer instructions, and AHJ requirements before treating the formula result as final.

For a chart record, use the Single-Phase vs Three-Phase Chart when the next question is which voltage and phase model applies. Use the kVA to Amps Chart when the formula result needs line-current documentation before transformer, feeder, load-bank, or equipment review.

Three-Phase Power Formulas

Real Power (Watts/kW)

Method Formula When to Use
Line Values P = √3 × V_L × I_L × PF Most common (line-to-line voltage)
Phase Values P = 3 × V_ph × I_ph × PF When phase values known

Calculator checkpoint: real power from line values

Before solving real power, collect the actual line-to-line voltage, line current, and power factor. Then run the formula or calculator for that specific load and carry the result into the next equipment check instead of reusing a sample result.

Apparent Power (VA/kVA)

Method Formula
Line Values S = √3 × V_L × I_L
Phase Values S = 3 × V_ph × I_ph

Reactive Power (VAR/kVAR)

Q = √3 × V_L × I_L × sin(θ)
Q = √(S² - P²)

Line vs Phase Values

Understanding the Difference

Term Description Symbol
Line Voltage Voltage between any two lines (L-L) V_L or V_LL
Phase Voltage Voltage from line to neutral (L-N) V_ph or V_LN
Line Current Current in the supply line I_L
Phase Current Current through each winding I_ph

Star (Wye) Connection Formulas

V_L = √3 × V_ph
V_ph = V_L / √3

I_L = I_ph

Common Wye Voltages:

Line Voltage Phase Voltage
208V 120V
400V 230V
480V 277V
600V 347V

Delta Connection Formulas

V_L = V_ph

I_L = √3 × I_ph
I_ph = I_L / √3

Star vs Delta Comparison

Voltage and Current Relationships

Parameter Star (Y) Delta (Δ)
Line Voltage V_L = √3 × V_ph V_L = V_ph
Phase Voltage V_ph = V_L ÷ √3 V_ph = V_L
Line Current I_L = I_ph I_L = √3 × I_ph
Phase Current I_ph = I_L I_ph = I_L ÷ √3
Power P = √3 × V_L × I_L × PF P = √3 × V_L × I_L × PF
Neutral Available Not available

When to Use Each

Configuration Best For
Star (Wye) Distribution systems, single-phase loads from 3-phase, motors that need reduced starting current
Delta Motor running, higher starting torque, transmission (no neutral needed)

Three-Phase Current Calculations

Current from Power (Most Common)

I = P / (√3 × V × PF)

Example: 50 kW motor, 480V, PF = 0.87

I = 50,000W / (1.732 × 480V × 0.87)
I = 50,000 / 723.5
I = 69.1A per phase

Current from kVA

I = kVA × 1000 / (√3 × V)

Example: 75 kVA transformer, 480V

I = 75,000 / (1.732 × 480)
I = 75,000 / 831.4
I = 90.2A

Current from HP (Motors)

I = HP × 746 / (√3 × V × Eff × PF)

Example: 50 HP motor, 480V, Eff = 0.92, PF = 0.87

I = 50 × 746 / (1.732 × 480 × 0.92 × 0.87)
I = 37,300 / 665.6
I = 56.0A

Three-Phase Voltage Calculations

Standard Three-Phase Voltages

Nominal Line-to-Line Line-to-Neutral Use
208/120V 208V 120V Commercial
240V 240V 139V Commercial Delta
480/277V 480V 277V Industrial
600/347V 600V 347V Industrial (Canada)

Voltage Drop in Three-Phase

V_drop = √3 × I × (R × cos(θ) + X × sin(θ)) × L

For approximate calculation (copper wire):

V_drop (%) = (√3 × I × L × ρ) / (A × V) × 100

Where:

  • I = Line current (A)
  • L = One-way length (feet)
  • ρ = Resistivity constant
  • A = Wire cross-section area

→ Use Voltage Drop Calculator for accurate sizing.


Motor Full Load Current (FLC) Tables

Three-Phase Motor FLC at 460V

Based on NEC Table 430.250:

HP FLC (A) HP FLC (A)
1 2.1 30 40
2 3.0 40 52
3 4.8 50 65
5 7.6 60 77
7.5 11 75 96
10 14 100 124
15 21 125 156
20 27 150 180
25 34 200 240

Motor FLC at Different Voltages

HP 208V 230V 460V 575V
10 30.8 28 14 11
25 74.8 68 34 27
50 143 130 65 52
100 273 248 124 99

→ Use Full Load Current Calculator for NEC table FLC values, or Motor Current Calculator for formula-current comparison.


Transformer Sizing

Three-Phase Transformer kVA

kVA = √3 × V × I / 1000

Or from load:

kVA = kW / PF

Standard 3-Phase Transformer Sizes

15, 30, 45, 75, 112.5, 150, 225, 300, 500, 750, 1000, 1500, 2000, 2500 kVA

Sizing Example:

Load: 200 kW, PF = 0.85

kVA = 200 / 0.85 = 235.3 kVA
Select next size: 300 kVA transformer

Worked Examples

Example 1: Calculate 3-Phase Power

Given: 480V system, 50A per line, PF = 0.9

Solution:

P = √3 × V × I × PF
P = 1.732 × 480 × 50 × 0.9
P = 37,413W = 37.4 kW

Example 2: Current for Known Load

Given: 100 kW load, 208V, 3-phase, PF = 0.85

Solution:

I = P / (√3 × V × PF)
I = 100,000 / (1.732 × 208 × 0.85)
I = 100,000 / 306.2
I = 326.6A

Example 3: Star to Delta Conversion

Given: Star-connected motor, V_ph = 230V, I_ph = 10A

For Star:

V_L = √3 × V_ph = 1.732 × 230 = 398.4V
I_L = I_ph = 10A

If reconnected in Delta at same line voltage:

V_ph = V_L = 398.4V
I_ph = V_ph / Z = 398.4 / 23 = 17.3A (assuming same impedance)
I_L = √3 × I_ph = 1.732 × 17.3 = 30A

Power increases 3× in Delta!

Example 4: Generator Sizing

Given: Facility load 150 kW, PF = 0.8, want 25% reserve

Solution:

Required kVA = kW / PF = 150 / 0.8 = 187.5 kVA
With 25% reserve: 187.5 × 1.25 = 234.4 kVA
Select: 250 kVA generator

Unbalanced Load Calculations

Single-Phase Load on Three-Phase

For single-phase load connected line-to-neutral:

I_line = kW × 1000 / (V_ph × PF)

Balancing Three-Phase Loads

To balance loads across phases:

  1. Calculate total load per phase
  2. Move loads to equalize current
  3. Target within 10% imbalance

Common Mistakes to Avoid

Mistake Why It's Wrong Correct Approach
Forgetting √3 factor Power calculation off by 1.732 Always use √3 for 3-phase
Using wrong voltage Line vs phase confusion Clarify V_LL or V_LN before calculating
Ignoring power factor Undersized conductors Include PF for AC loads
Same current Star/Delta Currents differ by √3 Apply correct conversion

Related Calculators

Calculator Use When...
3-Phase Power Calculator Power and current calculations
Full Load Current Calculator Motor FLC lookup
Motor Current Calculator Formula-current comparison
Transformer Sizing Transformer kVA selection
Voltage Drop Calculator Wire sizing for distance

Summary

Essential Three-Phase Formulas:

Calculate Formula
Power P = √3 × V_L × I_L × PF
Current I = P / (√3 × V × PF)
kVA S = √3 × V_L × I_L

Star vs Delta:

  • Star: V_L = √3 × V_ph, I_L = I_ph
  • Delta: V_L = V_ph, I_L = √3 × I_ph

Remember: √3 = 1.732


FAQ

What does √3 represent in three-phase?

√3 (1.732) is the mathematical factor that relates line and phase values due to the 120° phase shift between phases. It appears in all balanced three-phase power calculations.

How do I convert single-phase to three-phase current?

Three-phase current is lower than single-phase for the same power. Divide single-phase current by √3 (1.732) for equivalent three-phase current at the same voltage.

What is the difference between Star and Delta?

Star (Wye) has a neutral connection and different line/phase voltages (V_L = √3 × V_ph). Delta has no neutral, and line voltage equals phase voltage, but line current is √3 times phase current.

Why is 480V common for industrial?

480V three-phase offers efficient power transmission with lower currents than 208V or 240V systems. Lower current means smaller conductors and lower losses for heavy industrial loads.

How do I calculate amps from HP for a 3-phase motor?

Use I = (HP × 746) / (√3 × V × Eff × PF) or refer to NEC Table 430.250 for standard FLC values. Always use nameplate data when available.

Tags

three-phasestardeltapowercurrent

Related Calculators

Frequently Asked Questions

What is the 3-phase power formula?
P (watts) = √3 × V_L × I_L × PF, where V_L is line-to-line voltage, I_L is line current, and PF is power factor. In kW: P = (√3 × V_L × I_L × PF) ÷ 1000. For apparent power, use S = (√3 × V_L × I_L) ÷ 1000 and verify the entered values in the calculator.
How do I calculate amps from kW in a 3-phase system?
I (amps) = P × 1000 ÷ (√3 × V × PF). For kVA loads, use I = kVA × 1000 ÷ (√3 × V). For motor HP, use HP × 746 ÷ (√3 × V × efficiency × PF), then compare the result with nameplate data or the correct NEC motor table.
What is the difference between line voltage and phase voltage in 3-phase?
In a star (wye) system: line voltage V_L = √3 × phase voltage V_ph (e.g., 480V line → 277V phase). Line current equals phase current. In a delta system: line voltage equals phase voltage (V_L = V_ph), but line current I_L = √3 × phase current I_ph. The √3 = 1.732 factor arises from the 120° phase displacement between the three phases.
How do I calculate current for a 480V 3-phase motor?
For a motor with known HP, compare formula current with the appropriate NEC table and the motor nameplate. Use I = HP × 746 ÷ (√3 × V × efficiency × PF) for an engineering estimate, then use the motor-current or full-load-current calculator for the actual HP, voltage, and phase.
Why is √3 (1.732) used in 3-phase formulas?
√3 = 1.732 appears in all balanced 3-phase calculations because the three phase voltages are displaced by 120°. The vector sum of two phase voltages separated by 120° has magnitude √3 times the individual phase voltage. This means: for wye, V_line = √3 × V_phase (208V system has 120V per phase); for delta, I_line = √3 × I_phase. Without the √3 factor, power calculations would be off by 73%.

Need to Calculate Something?

Use our electrical calculators to solve your engineering problems quickly and accurately.