Electrical reference chart
Motor Starting Current Chart
Use this worksheet after the calculator result to keep running current, locked-rotor multiplier, starter method, estimated line starting current, starting kVA, and voltage-sag notes in one motor-start screen. A 50 HP, 460 V motor using 65 A FLA and a 6x direct-on-line start screens at 390 A inrush and about 311 kVA before soft-starter, VFD, transformer, and feeder checks.
Quick reference table
A motor starting current chart is a calculator-led planning screen for inrush, not a generic motor table. For a 50 HP, 460 V motor with 65 A FLA and a 6x direct-on-line multiplier, the line starting current is 390 A and starting kVA is about 311 kVA before the electrician compares the result with the controller, transformer, feeder, and utility limit.
Motor starting result worksheet
| Result item | Record from calculator | Field use before the next decision |
|---|---|---|
| Running current basis | FLA, FLC, or nameplate current | Confirm which current value drove the inrush estimate |
| Locked-rotor multiple | Selected LRA multiple or code-letter estimate | Replace with manufacturer data when available |
| Starter method | DOL, soft starter, VFD, autotransformer, or tap setting | Keep method effects separate from motor current |
| Line starting current | Estimated amperes at the feeder | Compare with upstream device and transformer notes |
| Starting kVA | Apparent-power screen | Use for utility, transformer, and voltage-sag conversation |
Starter method screening notes
| Starting method | What the chart should record | Common field check |
|---|---|---|
| Direct-on-line | Highest inrush screen from the selected multiplier | Check nuisance trip and voltage-sag exposure |
| Soft starter | Current-limit setting and ramp time | Check that reduced current still leaves enough acceleration torque |
| VFD start | Drive input current and bypass condition if present | Check drive manual, overload setup, and available fault current |
| Autotransformer or reduced-voltage tap | Tap percent and line-current factor | Check transition timing and controller ratings |
Formula basis
Estimated line starting current = FLA x locked-rotor multiple x starting-method line-current factor.
- FLA is the running-current basis used by the calculator, ideally tied to nameplate or documented table current.
- Locked-rotor multiple is the selected inrush multiplier or manufacturer value.
- Starting-method factor reflects DOL, soft starter, VFD, autotransformer, wye-delta, or other reduced-voltage behavior.
- Starting kVA is the apparent-power screen calculated from voltage and estimated line starting current.
Worked examples
Assumptions. Balanced load and line-to-line voltage assumptions behind this chart.
- The worksheet uses calculator multipliers as planning inputs; manufacturer locked-rotor data, controller settings, and nameplate data should replace assumptions when available.
- Voltage sag, acceleration time, nuisance tripping, transformer stiffness, and utility starting limits require separate project checks.
- The result is a line-current estimate, so motor current, controller input current, and bypass current should be labeled separately when they differ.
Code and standard notes. Planning limits that should be checked before final equipment selection.
- Use this chart as a calculator-led planning worksheet; verify nameplate data, manufacturer starting data, utility requirements, equipment ratings, and AHJ expectations before final use.
How to use this chart
Worksheet checklist. Record source basis, review gaps, and assumptions before using the chart result.
- Record current basisWrite whether the current came from nameplate FLA, table FLC, measured current, or a formula estimate before interpreting inrush.
- Record method settingsDocument the selected starting method and any current limit, tap, ramp time, bypass mode, or controller setting that changes line current.
- Record source notesAdd transformer size, feeder length, available fault current, or utility-starting notes when those values affect the next field decision.
Common mistakes to avoid. Review these before turning chart current into an equipment decision.
- Using a generic locked-rotor multiplier without recording whether actual motor or controller data is available for the installation.
- Treating reduced line current as proof that acceleration torque, voltage sag, and upstream protection are acceptable.
- Comparing two starter methods without labeling whether the value is motor current, line current, drive input current, or bypass current.
Frequently asked questions
These answers explain how to use the chart without turning a quick reference into a final design decision.
Is locked-rotor current the same as line starting current?
Can this chart select the starter?
Related calculators
- Motor Starting Current CalculatorScreen induction-motor starting current and compare DOL, star-delta, soft starter, VFD, and autotransformer starts.
- Motor Current CalculatorCompare NEC table full-load current with formula current, screen starting current, and check preliminary AC motor branch-circuit sizing.
- Full Load Current CalculatorNEC Table 430.248/430.250 motor full load current (FLC) lookup with conductor sizing, overload-basis reminder, and branch-circuit breaker requirements
Related charts
- HP to Amps ChartUse this HP to amps chart as an early motor-current screen; open the motor calculator for voltage, efficiency, PF, NEC FLC, and nameplate FLA.
- Motor Full Load Amps ChartPlan motor full-load amp work by separating table FLC, nameplate FLA, formula estimates, starting current, overloads, and branch-circuit protection.
- Motor Power HP kW ChartUse a motor power HP kW chart to document horsepower, mechanical output, electrical input, kVA, kVAR, power factor, efficiency, and current context after the calculator result.