Electrical reference chart
HP to Amps Chart
Use this motor-current screen when horsepower is known but the project still needs nameplate FLA, starting current, protection, or conductor review.
Quick reference table
HP-to-amps is a motor load estimate, not a substitute for motor nameplate FLA or NEC motor full-load current workflows. A 10 HP at 480 V 3-phase motor estimates about 11.2 A with the chart assumptions. Use it early when reviewing a pump, fan, compressor, conveyor, or shop motor schedule, then move to the motor calculator with voltage, phase, efficiency, power factor, nameplate current, and starting-current context.
Formula-based motor running-current screen
| Motor size | 240 V 1-phase | 208 V 3-phase | 480 V 3-phase | Assumption |
|---|---|---|---|---|
| 1 HP | 4.3 A | 3.0 A | 1.3 A | 90% eff, 0.80 PF |
| 3 HP | 13.0 A | 9.0 A | 3.9 A | 90% eff, 0.80 PF |
| 5 HP | 21.6 A | 15.0 A | 5.6 A | 90% eff, 0.80 PF |
| 10 HP | 43.2 A | 29.9 A | 11.2 A | 90% eff, 0.80 PF |
| 25 HP | 107.9 A | 74.8 A | 28.1 A | 90% eff, 0.80 PF |
Which motor current value belongs in which decision
| Decision | Current basis to verify | Why the chart is not enough |
|---|---|---|
| Load estimate | Formula current or nameplate input current | Good for early panel or generator screening |
| Conductor and branch circuit | Adopted motor sizing path and table/nameplate basis | Motor rules can differ from formula current |
| Overload protection | Motor nameplate current and overload instructions | Nameplate FLA is usually central |
| Starting review | Locked-rotor, inrush, or starter method | Running current does not show voltage dip |
How to use this chart
Use it before the nameplate is complete
Use the chart for early pump, fan, compressor, conveyor, or shop-equipment screening when horsepower is known but full motor data is not ready.
Record motor phase and voltage
Write the actual motor connection voltage and whether the motor is single-phase or three-phase before comparing rows.
Separate running and starting current
Use this page for running-current estimates only, then use the starting-current workflow for inrush, voltage dip, or generator sizing concerns.
Move code work to the motor calculator
Before conductors or protection are selected, use the motor calculator and verify nameplate, adopted NEC, manufacturer, and AHJ requirements.
Worksheet checklist
- Record horsepower sourceIdentify whether HP came from a motor nameplate, equipment submittal, pump schedule, preliminary design, or replacement request.
- Attach efficiency and PF basisUse measured, nameplate, manufacturer, or conservative assumed values for efficiency and PF, and label the assumption clearly.
- Document motor decision pathMark whether the current is for load estimating, conductor review, overload setup, starter selection, generator sizing, or troubleshooting.
Common mistakes to avoid
- Using the formula estimate as if it were the required NEC motor full-load current for every downstream sizing decision.
- Ignoring efficiency and power factor, which can make estimated current look lower than real motor current.
- Using running current for starting-current or voltage-dip questions where locked-rotor behavior matters.
Formula basis
Single phase estimate: A = HP x 746 / (V x efficiency x PF). Three phase estimate: A = HP x 746 / (1.732 x VLL x efficiency x PF).
- HP is mechanical horsepower.
- Efficiency is motor efficiency entered as a decimal.
- PF is motor power factor entered as a decimal.
- V or VLL is the voltage used by the motor connection.
Worked examples
5 HP fan motor at 480 V three-phase
5 x 746 / (1.732 x 480 x 0.90 x 0.80) = about 6.2 A as a running-current screen before nameplate and protection review.
3 HP single-phase shop motor at 240 V
3 x 746 / (240 x 0.88 x 0.78) = about 13.6 A using the documented efficiency and PF assumptions.
Assumptions
- The table is formula-based and does not reproduce NEC motor full-load current tables.
- Nameplate current, service factor, duty, design letter, starting method, and manufacturer instructions can change the motor workflow.
- The table assumes running current, not locked-rotor or starting current.
Code and standard notes
- For motor conductors, overloads, short-circuit and ground-fault protection, controller selection, and disconnecting means, verify the adopted NEC edition, equipment nameplate, manufacturer instructions, and AHJ requirements.
Related calculators
Motor Current Calculator
Compare NEC table full-load current with formula current, screen starting current, and check preliminary AC motor branch-circuit sizing.
Full Load Current Calculator
NEC Table 430.248/430.250 motor full load current (FLC) lookup with conductor sizing, overload-basis reminder, and branch-circuit breaker requirements
Motor Starting Current Calculator
Screen induction-motor starting current and compare DOL, star-delta, soft starter, VFD, and autotransformer starts.
Related charts
Single Phase vs Three Phase Chart
Compare single-phase, split-phase, and balanced three-phase calculation contexts before choosing a power or motor calculator.
Power Factor Correction Chart
Estimate capacitor kVAR for power-factor correction and document the utility, harmonic, switching, and equipment checks needed before selection.
Frequently asked questions
These answers explain how to use the chart without turning a quick reference into a final design decision.