Motors & Loads calculator

Motor Protection Calculator

Use this page after the base motor current has already been identified. A 10 HP, 460 V, three-phase Design B motor screens at 14 A FLC, 16.1 A overload, 35 A inverse-time breaker, and 17.5 A conductor ampacity before listed-equipment review. The Full Load Current Calculator handles NEC Table 430.248/430.250 lookup, the Motor Current Calculator handles formula running-current comparison, and the Motor Starting Current Calculator handles inrush and locked-rotor screening.

Updated July 10, 2026

Calculator Inputs

Field notes

Calculation Results

Enter values above to see calculation results

Opens in a new tabOpens in a new tabOpens in a new tab
Calculation history

Example Calculations

10 HP, 460V Three-Phase Motor Protection ScreenUse nameplate FLA for overload review and NEC table FLC for the branch-circuit short-circuit and ground-fault screen.InputsMotor Power: 10Voltage: 460Phases: Three phaseNec Table FLC: 14Service Factor: 1Branch Device Type: Inverse Time Breaker
200 HP, 460V Branch-Circuit Fault Protection ScreenUse the NEC table FLC from the full-load-current workflow before applying the selected fault-protection device multiplier.InputsMotor Power: 200Voltage: 460Phases: Three phaseNec Table FLC: 240Branch Device Type: Inverse Time Breaker

How to Use

Motor Protection Calculator for NEC Article 430 Workflows

This page is for protection review, not base-current discovery. Start with the correct current basis, then use the protection result as a preliminary screen before selecting listed equipment and final settings.

1. Choose the correct current basis

Protection task Current basis Next step
Overload protection Actual motor nameplate FLA Apply the service-factor and temperature-rise rule for the installed motor.
Branch-circuit short-circuit and ground-fault protection NEC table FLC from the applicable motor table Apply the device percentage and standard-size rules for the selected device type.
Starting-current review Locked-rotor or starting-current data Use the starting-current workflow when nuisance tripping or source stiffness is the question.

2. Review overload protection separately

Overload protection protects the motor from sustained overcurrent and overheating. For common continuous-duty motors, the overload setting is based on the actual nameplate FLA. Motors with a service factor of 1.15 or higher, or a qualifying temperature rise, can commonly be reviewed at 125% of nameplate FLA; other motors are commonly reviewed at 115%. Confirm the final device selection against the adopted NEC edition and the overload-device instructions.

3. Review branch-circuit fault protection separately

Branch-circuit short-circuit and ground-fault protection has a different job. It must clear high-current faults while still carrying normal motor starting current. For this part of the workflow, use the NEC table full-load current from the Full Load Current Calculator, then apply the selected device type. A common inverse-time breaker screen uses 250% of NEC table FLC before standard-size review.

4. Do not use one current value for every decision

A motor circuit can involve formula running current, nameplate FLA, NEC table FLC, locked-rotor current, and measured operating current. This page uses those values for protection review after the current basis is already known.

For the current basis, use the Full Load Current Calculator when the job is NEC table FLC lookup, the Motor Current Calculator when the job is formula running-current comparison, and the Motor Starting Current Calculator when the concern is inrush or locked-rotor current. Then return here for overload, branch-circuit, and conductor-protection review.

Common Applications

Reviewing motor overload settings from actual nameplate FLA
Screening branch-circuit short-circuit and ground-fault protection from NEC table FLC
Separating overload protection from fault protection in motor circuits
More applications. Open to review 3 additional use cases.
Checking whether nuisance tripping belongs in starting-current review instead of overload adjustment
Documenting a preliminary protection workflow before final listed-device selection
Coordinating motor protection review with FLC lookup, formula current, and starting-current tools

Frequently Asked Questions

Should motor overload protection use nameplate FLA or NEC table FLC?
Use actual motor nameplate FLA for overload protection. NEC table FLC is used for branch-circuit conductor sizing and branch-circuit short-circuit and ground-fault protection, so it should not be treated as the overload-current basis.
When should I use the Full Load Current Calculator instead of this page?
Use the Full Load Current Calculator when the task is the NEC Table 430.248 or 430.250 lookup by horsepower, voltage, and phase. Return to this page after that value is known and the task becomes overload or branch-circuit protection review.
What is the difference between overload protection and short-circuit protection?
Overload protection responds to sustained overcurrent that can overheat the motor. Branch-circuit short-circuit and ground-fault protection responds to high-current faults and must also tolerate normal motor starting current. The two functions use different sizing logic.
Does this page select the final breaker, fuse, starter, or relay?
No. It provides a preliminary calculation and current-basis check. Final selection depends on the adopted NEC edition, listed equipment, manufacturer instructions, available fault current, time-current coordination, and site conditions.
Where does starting current fit in the protection workflow?
Starting current matters when reviewing nuisance tripping, source stiffness, soft-starter settings, VFD behavior, or locked-rotor conditions. Use the Motor Starting Current Calculator for that workflow, then return here only if the question is protection-device review.

Related Calculators

Browse all calculators