Conductor formula tool

Wire Resistance Calculator

Estimate one-way and round-trip conductor resistance from material, size, and length without turning the result into wire sizing.

Calculate Wire Resistance

Enter conductor material, size, and one-way length to estimate one-way and round-trip resistance near 20 C.

Result

Resistance

0.1588 ohm

One-way conductor, 12 AWG, near 20 C.

Total resistance

0.3175 ohm

Result notes

Keep the entered values, assumptions, and result together when adding this calculation to job notes or submittal records. Final installation choices should align with the applicable code edition, equipment listing, manufacturer instructions, local amendments, and AHJ requirements.

Formula and field context

Estimate one-way and round-trip conductor resistance from material, size, and length without turning the result into wire sizing.

Formula context

Wire Size Chart

A wire size chart is useful only when it keeps the field sequence visible: calculated load first, usable ampacity second, terminal temperature and derating third, then voltage drop and equipment instructions. Use the calculator result as the starting point and verify the adopted NEC edition, manufacturer data, and AHJ requirements before treating the conductor as ready for the job.

Formula

Conductor planning screen = calculated load plus duty factors, then compare usable ampacity, terminal limit, voltage-drop target, and equipment instructions.

Variables to keep with the result

  • Calculated load is the amperes from the load schedule, nameplate, or calculator result.
  • Usable ampacity is the conductor value after material, insulation, terminal temperature, ambient correction, and conductor-count adjustment are considered.
  • Voltage drop is a performance screen that can require a larger conductor even when ampacity is acceptable.

Formula and variables

Conductor resistance can be estimated from R = rho x L / A. R is resistance in ohms, rho is material resistivity, L is conductor length, and A is conductor cross-sectional area. This worksheet uses common copper and aluminum resistivity near 20 C, converts feet to meters, converts mm2 to square meters, and returns one-way and round-trip resistance for documentation.

U.S. field context and example

Wire resistance supports voltage-drop notes, test-record comparisons, temporary lead planning, low-voltage control work, and troubleshooting where measured resistance needs a reasonableness check. For example, a 100 ft one-way run of 12 AWG copper is about 0.159 ohm near 20 C, or about 0.318 ohm round trip. The round-trip value matters when current leaves and returns through two conductors, such as a simple two-wire DC or single-phase circuit path.

Assumptions and limits

The result is an electrical resistance estimate, not a conductor selection. Stranding, actual conductor area, temperature, alloy, splices, terminations, and measurement lead resistance can change the field value. Use the voltage-drop calculator when load current and acceptable drop must be reviewed. Use the wire-size and ampacity calculators when the conductor must be selected for an installation.

Common mistakes

Common mistakes include using one-way resistance when the circuit path is round trip, mixing feet and meters, treating aluminum like copper, and ignoring temperature. When a resistance value will be compared to a meter reading, document whether the measured path includes one conductor, two conductors, equipment bonding paths, terminations, or connected loads.

Common Questions

Why show one-way and round-trip resistance?
Voltage drop and loop measurements often use the complete current path. A one-way conductor and a two-conductor round trip can produce different resistance notes.
Can this select wire size?
No. It estimates resistance. Use wire-size, ampacity, voltage-drop, and code workflows when selecting an installed conductor.
Does resistance change with temperature?
Yes. Copper and aluminum resistance rise as conductor temperature rises. Use the temperature-resistance tool when temperature correction is the main task.