Planning referenceCode-sensitiveLast reviewed April 29, 2026

Electrical reference chart

Wire Size Chart

Use this wire size chart after the calculator result to document why a conductor size was selected, which inputs controlled the result, and what must be checked before ordering wire or pulling a circuit.

Open calculator

Quick reference table

A wire size chart is useful only when it keeps the field sequence visible: calculated load first, usable ampacity second, terminal temperature and derating third, then voltage drop and equipment instructions. Use the calculator result as the starting point and verify the adopted NEC edition, manufacturer data, and AHJ requirements before treating the conductor as ready for the job.

Wire size field decision order

Wire size field decision order
StepRecord from the jobWhy it can control size
Load basisCalculated amps, voltage, phase, and continuous dutySets the minimum current the conductor must carry
Conductor familyCopper or aluminum, insulation type, raceway or cable methodChanges resistance, ampacity basis, and termination expectations
Termination limitEquipment lug temperature rating and conductor material allowedCan cap the usable ampacity below the insulation rating
Adjustment conditionsAmbient temperature, rooftop exposure, grouping, and current-carrying countCan reduce the conductor ampacity used for planning
Performance checkOne-way distance and project voltage-drop targetMay make a larger conductor practical for long runs

Common result-area follow-up checks

Common result-area follow-up checks
Calculator result showsField question to answerNext action
Ampacity controlsAre terminals, ambient, and bundling already reflected?Review ampacity chart and document the limiting factor
Voltage drop controlsIs the run length or voltage-drop target driving a larger size?Keep the larger size and note the performance basis
Aluminum selectedAre lugs listed and torque instructions available?Verify equipment instructions before procurement
Borderline resultWould a future load or field routing change affect the selection?Review spare capacity before the pull is scheduled

How to use this chart

1

Start from the result, not memory

Use the calculator output as the job record, then confirm which input controlled the conductor size: load current, terminal rating, derating, or voltage drop.

2

Separate heat from performance

Ampacity protects the conductor from overheating, while voltage drop protects equipment performance. Keep both screens visible before calling the size acceptable.

3

Close with equipment notes

Before ordering conductor, document lug material, temperature rating, torque instructions, raceway plan, and any manufacturer requirements that affect the installation.

Formula basis

Conductor planning screen = calculated load plus duty factors, then compare usable ampacity, terminal limit, voltage-drop target, and equipment instructions.

  • Calculated load is the amperes from the load schedule, nameplate, or calculator result.
  • Usable ampacity is the conductor value after material, insulation, terminal temperature, ambient correction, and conductor-count adjustment are considered.
  • Voltage drop is a performance screen that can require a larger conductor even when ampacity is acceptable.

Worked examples

Long 240 V feeder result

The calculator may show that the minimum ampacity size passes, but the voltage-drop result pushes the feeder one size larger. Keep the performance reason in the worksheet so the field crew does not downsize it later.

Aluminum branch circuit review

A planning result using aluminum conductors still needs terminal material, lug listing, oxide inhibitor requirements where specified, and torque instructions checked before the conductor choice is released.

Frequently asked questions

These answers explain how to use the chart without turning a quick reference into a final design decision.

Can I pick the conductor directly from this chart?
No. Use the chart to keep the work sequence organized, then use the wire size calculator and verify the result against the adopted NEC edition, equipment instructions, and AHJ requirements.
Why can the calculator show a larger conductor than the ampacity minimum?
Long distance, aluminum material, voltage-drop target, terminal limits, or adjustment conditions can all move the practical conductor size above a simple ampacity screen.
Should breaker size decide wire size by itself?
No. Breaker size is part of the overcurrent protection review, but conductor selection starts with calculated load and must also consider ampacity, terminals, derating, voltage drop, and equipment instructions.