intermediate

NEC Derating Chart | Ampacity & Temp Factors

Use NEC derating chart/table for temperature correction, conductor-count adjustment, terminal limits, and 10 AWG THHN example.

14 min read
Updated 8/5/2026
EleCalculator Team

Quick answer: Adjusted Ampacity = Base Ampacity × Temperature Factor × Current-Carrying Conductor Adjustment Factor. Example: 10 AWG THHN with 90°C insulation, 45°C ambient, and 9 current-carrying conductors gives 40 A × 0.87 × 0.70 = 24.4 A before terminal and conductor-protection checks. Use the Ampacity Calculator when conductor material, terminal rating, rooftop exposure, or multiple conditions must stay with the result.

NEC edition note: NFPA 70 is adopted and amended by jurisdiction. Use the NEC edition enforced by the AHJ for the project location, then verify Article 310 table references, terminal ratings, equipment markings, and local amendments before final conductor or overcurrent decisions.

NEC derating chart/table short answer

Read the derating chart in this order: base ampacity, temperature correction, conductor-count adjustment. For the common 10 AWG THHN example, use the 90°C ampacity basis for adjustment, then apply the temperature and conductor-count factors:

10 AWG THHN adjusted ampacity = 40 A × 0.87 × 0.70 = 24.4 A

The 24.4 A value is the adjusted ampacity screen before terminal limits, small-conductor protection, equipment markings, local amendments, and AHJ review. Use the calculator when the installation has more than this single example.

Calculator Follow-Up

How do I derate conductor ampacity?

Adjusted Ampacity = Base Ampacity × Temperature Factor × Current-Carrying Conductor Adjustment Factor
Derating Type Reference Point Edition Check Factor Range
Temperature Article 310 temperature table Verify adopted NEC edition 0.41 – 1.08
Conductor Count Article 310 adjustment factors Verify adopted NEC edition 0.35 – 1.00
Rooftop Solar Rooftop ambient-temperature rule Verify adopted NEC edition +14°C to +33°C adder
Combined Multiply factors Keep terminal limits separate 0.20 – 1.00

Use the Ampacity Calculator for automatic derating.


After the Derating Result

Once adjusted ampacity is known, continue the installation workflow instead of stopping at the factor math:

Next decision Use
Conductor gauge after derating Wire Size Calculator
Physical raceway fill Conduit Fill Calculator
Long-run voltage drop Voltage Drop Calculator
Device size and small-conductor limits Breaker Sizing Calculator
Ambient-temperature record Temperature Correction Chart
Bundling documentation Conductor Bundling Derating Chart
Terminal rating handoff Terminal Temperature Rating Chart
Use this guide as a planning reference. Final conductor and overcurrent selections still need the adopted NEC edition, terminal ratings, equipment markings, local amendments, and AHJ review.

Why Derate Ampacity?

Heat Is the Enemy

Conductors have maximum operating temperatures. Derating accounts for:

  • High ambient temperature - Less heat can be dissipated
  • Multiple conductors - Mutual heating reduces capacity
  • Rooftop installations - Solar heat increases ambient

Consequences of Not Derating

  • Insulation breakdown
  • Shortened conductor life
  • Fire hazard
  • Failed inspection or adopted-code conflict

Temperature Correction Factors

NEC Table 310.15(B)(1) - Temperature Correction

For ambient temperatures other than 30°C (86°F):

Ambient °C Ambient °F 60°C 75°C 90°C
21-25 70-77 1.08 1.05 1.04
26-30 78-86 1.00 1.00 1.00
31-35 87-95 0.91 0.94 0.96
36-40 96-104 0.82 0.88 0.91
41-45 105-113 0.71 0.82 0.87
46-50 114-122 0.58 0.75 0.82
51-55 123-131 0.41 0.67 0.76
56-60 132-140 0.58 0.71
61-65 141-149 0.47 0.65
66-70 150-158 0.33 0.58
71-75 159-167 0.50
76-80 168-176 0.41

Understanding Temperature Ratings

Rating Common Insulation Types
60°C TW, UF
75°C THW, THWN, RHW, XHHW (wet)
90°C THHN, THWN-2, XHHW-2, USE-2

Important: Even with 90°C wire, if terminals are rated 75°C, use 75°C ampacity!


Rooftop Temperature Adders

NEC 310.15(B)(2) - Rooftop Adders

For conduits exposed to sunlight on rooftops:

Height Above Roof Temperature Adder
0" - 1/2" +33°C (+60°F)
1/2" - 3-1/2" +22°C (+40°F)
3-1/2" - 12" +17°C (+30°F)
12" - 36" +14°C (+25°F)

Example: 40°C ambient, conduit 2" above roof:

Adjusted ambient = 40°C + 22°C = 62°C

Then use temperature correction table with 62°C.


Current-Carrying Conductor Adjustment Factors

NEC Table 310.15(C)(1) - More Than 3 Conductors

When more than 3 current-carrying conductors are in conduit:

Number of Conductors Adjustment Factor
4-6 0.80
7-9 0.70
10-20 0.50
21-30 0.45
31-40 0.40
41+ 0.35

What Counts as Current-Carrying?

Count:

  • Phase conductors (all)
  • Neutral with harmonics (>50% unbalanced)
  • Control circuit conductors if significant

Don't Count:

  • Equipment grounding conductors
  • Balanced neutral in 3-phase systems
  • Spare conductors (not energized)

Combined Derating Example

Step-by-Step Calculation

Given:

  • 6 × #8 AWG THHN conductors in conduit
  • Ambient temperature 40°C
  • Equipment terminals rated 75°C

Solution:

  1. Base ampacity (NEC Table 310.16):
  • #8 THHN at 90°C = 55A
  • But terminals 75°C, so use: 50A
  1. Temperature correction (40°C, 75°C column):
  • Factor = 0.88
  1. Current-carrying conductor adjustment (6 conductors):
  • Factor = 0.80
  1. Combined derating:
Adjusted = 50A × 0.88 × 0.80 = 35.2A

Result: The numeric ampacity screen is 35A per conductor before final equipment and AHJ review.


Quick Reference: Common Derating Scenarios

4-6 Conductors at Various Temperatures

Wire Size Base 75°C 35°C 40°C 45°C
12 AWG 25A 18.8A 17.6A 16.4A
10 AWG 35A 26.3A 24.6A 23.0A
8 AWG 50A 37.6A 35.2A 32.8A
6 AWG 65A 48.9A 45.8A 42.6A
4 AWG 85A 63.9A 59.8A 55.8A

Based on: 75°C ampacity × temp factor × 0.80 current-carrying conductor adjustment factor

7-9 Conductors at Various Temperatures

Wire Size Base 75°C 35°C 40°C 45°C
12 AWG 25A 16.5A 15.4A 14.4A
10 AWG 35A 23.0A 21.6A 20.1A
8 AWG 50A 32.9A 30.8A 28.7A
6 AWG 65A 42.8A 40.0A 37.3A
4 AWG 85A 55.9A 52.4A 48.9A

Based on: 75°C ampacity × temp factor × 0.70 current-carrying conductor adjustment factor


Special Derating Rules

Continuous Loads (NEC 210.20, 215.3)

For loads operating 3 hours or more continuously (e.g., HVAC, lighting, process equipment):

Conductor ampacity ≥ 125% of continuous load current

Or equivalently — when working from conductor ampacity to maximum allowed load:

Maximum continuous load = conductor adjusted ampacity × 0.80

Important: When both derating and the continuous-load rule apply, the 125% continuous factor is applied after temperature and current-carrying conductor adjustment — it is not a multiplicative derating factor but a minimum conductor sizing requirement:

Required conductor ampacity = (Continuous load × 1.25 + Non-continuous load) ÷ (Temp Factor × Conductor Adjustment Factor)

Example: 20 A continuous load, 40°C ambient, 6 conductors in conduit:

  • Required base ampacity (before derating): (20 × 1.25) = 25 A minimum
  • Derate: 25 A ÷ (0.88 × 0.80) = 25 A ÷ 0.704 = 35.5 A required
  • Select: 8 AWG THHN (50 A at 75°C) — derated to 35.2 A ⊼ 35.5 A, so select 6 AWG (65 A) → derated to 45.8 A > 25 A ✓

Neutral Conductor Derating

3-Phase, 4-Wire Systems:

  • Balanced loads: Neutral doesn't count
  • 50%+ neutral current: Count as current-carrying
  • Harmonic loads (VFDs, computers): Always count neutral

Bundled Cables

For cables bundled >24" without spacing:

  • Apply the same current-carrying conductor adjustment factors when bundled cables require that review
  • 24" minimum spacing = no derating required

Worked Examples

Example 1: Hot Attic Installation

Given:

  • 3 × #10 AWG THHN in attic (50°C ambient)
  • Feeding 30A circuit

Solution:

  1. Base ampacity #10 at 90°C: 40A
  2. Temperature factor (50°C, 90°C): 0.82
  3. Current-carrying conductor adjustment (3 conductors): 1.00
  4. Adjusted: 40A × 0.82 = 32.8A ✓

Result: 32.8A > 30A, so this numeric ampacity screen passes before final equipment and AHJ review.

Example 2: Rooftop HVAC

Given:

  • 3 × #6 AWG THHN on roof
  • Conduit 1" above roof deck
  • 35°C ambient temperature
  • 40A load

Solution:

  1. Rooftop adder (0-1/2" to 3.5"): +22°C
  2. Effective ambient: 35 + 22 = 57°C
  3. Base ampacity #6 at 90°C: 75A
  4. Temperature factor (57°C, 90°C): ~0.68
  5. Adjusted: 75A × 0.68 = 51A ✓

Result: 51A > 40A, so this numeric ampacity screen passes before final equipment and AHJ review.

Example 3: Multiple Circuit Conduit

Given:

  • 12 current-carrying conductors
  • Normal ambient (30°C)
  • Need 20A per circuit
  • Terminals rated 75°C

Solution:

  1. Current-carrying conductor adjustment factor (10-20): 0.50
  2. Temperature factor (30°C): 1.00
  3. Required base ampacity: 20A / 0.50 = 40A
  4. Select: #8 AWG (50A at 75°C) ✓

Verify: 50A × 1.00 × 0.50 = 25A > 20A ✓

Example 4: Hot Location with Many Wires

Given:

  • 8 conductors in conduit
  • 45°C ambient
  • Need 15A per circuit

Solution:

  1. Current-carrying conductor adjustment factor (7-9): 0.70
  2. Temp factor (45°C, 75°C): 0.82
  3. Combined: 0.70 × 0.82 = 0.574
  4. Required base: 15A / 0.574 = 26.1A
  5. Select: #10 AWG (35A at 75°C)

Verify: 35A × 0.574 = 20.1A > 15A ✓


Derating Calculation Workflow

For Any Installation:

  1. Determine load current
  2. Identify conditions:
  • Ambient temperature
  • Number of conductors
  • Continuous vs. non-continuous
  • Terminal ratings
  1. Look up factors:
  • Temperature correction
  • Current-carrying conductor adjustment
  1. Calculate:
Required Ampacity = Load / (Temp × Conductor Adjustment)
  1. Select conductor from NEC tables
  2. Verify the calculation both ways

Common Mistakes to Avoid

Mistake Why It's Wrong Correct Approach
Ignoring terminal ratings May exceed equipment limits Use lower of wire/terminal rating
Not counting harmonics Neutral may overheat Count neutral with harmonic loads
Forgetting rooftop adder Actual temp much higher Add temperature per table
Using 90°C for all Terminals usually 75°C Match to terminal rating

Related Calculators

Calculator Use When...
Ampacity Calculator Full derating calculations
Wire Size Calculator Selecting conductor gauge after derating is known
Conduit Fill Calculator Physical raceway fill
Voltage Drop Calculator Long run sizing

Summary

Temperature Correction:

  • Use the temperature-correction table from the adopted NEC edition
  • Match to insulation temperature rating
  • Add rooftop temperature where the adopted edition and installation conditions require it

Current-Carrying Conductor Adjustment:

  • 4-6 conductors: 80%
  • 7-9 conductors: 70%
  • 10-20 conductors: 50%

Combined:

Adjusted = Base × Temp Factor × Conductor Adjustment Factor

FAQ

When do I need to derate conductors?

Derate when: ambient exceeds 30°C, more than 3 current-carrying conductors in conduit, rooftop installation, or continuous loads (apply 125% rule).

Do I derate ground wires?

No, equipment grounding conductors are not current-carrying under normal conditions and do not count toward ampacity adjustment or need derating.

Which derating do I apply first?

Apply all factors by multiplication - the order doesn't matter mathematically. Calculate: Base × Temp × Conductor Adjustment = adjusted ampacity.

Can I use 90°C ampacity with 75°C terminals?

No. The limiting factor is the terminal. Use 75°C ampacity values, but you may use 90°C temperature correction factors since the wire itself can handle higher temps.

How do I handle neutral conductors?

For balanced 3-wire circuits, neutral doesn't count. For 4-wire with harmonic loads (LED, computers, VFDs), count neutral as current-carrying.

Tags

NECderatingtemperature correctionconduit fill

Related Calculators

Frequently Asked Questions

How do I apply NEC ampacity derating for temperature and current-carrying conductors?
Use the formula: Adjusted Ampacity = Base Ampacity × Temperature Correction Factor × Current-Carrying Conductor Adjustment Factor. Example: 10 AWG THHN at 45°C with 9 current-carrying conductors uses 40 A × 0.87 × 0.70 = 24.4 A before terminal and conductor-protection checks. Use the ampacity calculator when the job has more than one factor.
What conductors count as current-carrying for the adjustment factor?
Under the NEC Article 310 current-carrying-conductor review, count phase conductors and any neutral or control conductor that carries current under the adopted rule path. Equipment grounding conductors and balanced neutrals often are not counted, but nonlinear loads with significant triplen harmonics can change the neutral review. Verify the adopted NEC edition, load type, neutral current, equipment instructions, and AHJ expectations before finalizing the conductor count.
What temperature correction factor do I use if the wire is 90°C rated but the terminals are 75°C?
Use the 90°C temperature correction factor from NEC Table 310.15(B)(1), but apply it to the 75°C base ampacity from NEC Table 310.16. This is the standard practice under NEC 110.14(C)(1): terminal ratings limit the allowable current, but the wire’s actual insulation rating governs which temperature correction column you use. Example: 6 AWG THHN (90°C rated), terminals rated 75°C, 50°C ambient. Base ampacity = 65 A (75°C column, NEC 310.16). Temperature correction from the 90°C column at 50°C = 0.82. Adjusted = 65 A × 0.82 = 53.3 A. Do NOT use the 90°C base ampacity of 75 A — the terminal rating limits you to the 75°C column.
How does the NEC rooftop temperature adder affect derating?
Rooftop raceways can require an ambient-temperature adjustment when the adopted NEC edition and installation conditions call for it. Confirm the applicable rooftop rule, conduit height, direct-sun exposure, conductor insulation rating, and equipment terminal limits before applying the adjusted ambient temperature to the correction table.
Which NEC edition should I use for ampacity derating?
Use the NFPA 70 / National Electrical Code edition adopted by the AHJ for the project location. Article 310 table numbers, notes, and local amendments can vary by edition, so treat the factor workflow here as a calculation screen: confirm the adopted NEC edition, terminal ratings, equipment markings, manufacturer instructions, and local amendments before final conductor or overcurrent decisions.

Need to Calculate Something?

Use our electrical calculators to solve your engineering problems quickly and accurately.