intermediate

NEC Wire Derating Chart | 10 AWG = 24.4A

Use NEC wire derating chart/table: 10 AWG THHN at 45C with 9 current-carrying conductors gives 24.4A; compare temp, count and rooftop factors.

14 min read
Updated 6/7/2026
EleCalculator Team

Quick answer: Adjusted Ampacity = Base Ampacity × Temperature Factor × Current-Carrying Conductor Adjustment Factor. Example: 10 AWG THHN with 90°C insulation, 45°C ambient, and 9 current-carrying conductors → 40 A × 0.87 × 0.70 = 24.4 A before the 75°C terminal check. Use the Ampacity Calculator to combine the factors and the terminal check automatically. Use the Conduit Fill Calculator separately when the question is how many conductors physically fit in the raceway.

NEC edition note: This guide references section numbers primarily from the 2020 NEC. The 2023 NEC renumbered several subsections in Article 310. As of 2026, jurisdiction adoption varies — confirm the edition in force with your AHJ before finalizing designs.

NEC derating chart/table short answer

Read the derating chart in this order: base ampacity, temperature correction, conductor-count adjustment. Start with the conductor ampacity table and the terminal limit, choose the ambient-temperature factor for the insulation rating, then apply the current-carrying conductor count factor. For the common 10 AWG THHN example, that is 40 A × 0.87 × 0.70 = 24.4 A before the terminal check.

Quick Answer

How do I derate conductor ampacity?

Adjusted Ampacity = Base Ampacity × Temp Factor × Current-Carrying Conductor Adjustment Factor
Derating Type NEC 2020 Reference NEC 2023 Note Factor Range
Temperature 310.15(B)(1) Renumbered in 2023 0.41 – 1.08
Conductor Count 310.15(C)(1) Renumbered in 2023 0.35 – 1.00
Rooftop Solar 310.15(B)(2) Renumbered in 2023 +14°C to +33°C adder
Combined Multiply factors 0.20 – 1.00

Use the Ampacity Calculator for automatic derating.


After the Derating Result

Once adjusted ampacity is known, continue the installation workflow instead of stopping at the factor math:

Next decision Use
Conductor gauge after derating Wire Size Calculator
Physical raceway fill Conduit Fill Calculator
Long-run voltage drop Voltage Drop Calculator
Device size and small-conductor limits Breaker Sizing Calculator
Ambient-temperature record Temperature Correction Chart
Bundling documentation Conductor Bundling Derating Chart
Terminal rating handoff Terminal Temperature Rating Chart
Use this guide as a planning reference. Final conductor and overcurrent selections still need the adopted NEC edition, terminal ratings, equipment markings, local amendments, and AHJ review.

Why Derate Ampacity?

Heat Is the Enemy

Conductors have maximum operating temperatures. Derating accounts for:

  • High ambient temperature - Less heat can be dissipated
  • Multiple conductors - Mutual heating reduces capacity
  • Rooftop installations - Solar heat increases ambient

Consequences of Not Derating

  • Insulation breakdown
  • Shortened conductor life
  • Fire hazard
  • NEC code violation

Temperature Correction Factors

NEC Table 310.15(B)(1) - Temperature Correction

For ambient temperatures other than 30°C (86°F):

Ambient °C Ambient °F 60°C 75°C 90°C
21-25 70-77 1.08 1.05 1.04
26-30 78-86 1.00 1.00 1.00
31-35 87-95 0.91 0.94 0.96
36-40 96-104 0.82 0.88 0.91
41-45 105-113 0.71 0.82 0.87
46-50 114-122 0.58 0.75 0.82
51-55 123-131 0.41 0.67 0.76
56-60 132-140 0.58 0.71
61-65 141-149 0.47 0.65
66-70 150-158 0.33 0.58
71-75 159-167 0.50
76-80 168-176 0.41

Understanding Temperature Ratings

Rating Common Insulation Types
60°C TW, UF
75°C THW, THWN, RHW, XHHW (wet)
90°C THHN, THWN-2, XHHW-2, USE-2

Important: Even with 90°C wire, if terminals are rated 75°C, use 75°C ampacity!


Rooftop Temperature Adders

NEC 310.15(B)(2) - Rooftop Adders

For conduits exposed to sunlight on rooftops:

Height Above Roof Temperature Adder
0" - 1/2" +33°C (+60°F)
1/2" - 3-1/2" +22°C (+40°F)
3-1/2" - 12" +17°C (+30°F)
12" - 36" +14°C (+25°F)

Example: 40°C ambient, conduit 2" above roof:

Adjusted ambient = 40°C + 22°C = 62°C

Then use temperature correction table with 62°C.


Current-Carrying Conductor Adjustment Factors

NEC Table 310.15(C)(1) - More Than 3 Conductors

When more than 3 current-carrying conductors are in conduit:

Number of Conductors Adjustment Factor
4-6 0.80
7-9 0.70
10-20 0.50
21-30 0.45
31-40 0.40
41+ 0.35

What Counts as Current-Carrying?

Count:

  • Phase conductors (all)
  • Neutral with harmonics (>50% unbalanced)
  • Control circuit conductors if significant

Don't Count:

  • Equipment grounding conductors
  • Balanced neutral in 3-phase systems
  • Spare conductors (not energized)

Combined Derating Example

Step-by-Step Calculation

Given:

  • 6 × #8 AWG THHN conductors in conduit
  • Ambient temperature 40°C
  • Equipment terminals rated 75°C

Solution:

  1. Base ampacity (NEC Table 310.16):
  • #8 THHN at 90°C = 55A
  • But terminals 75°C, so use: 50A
  1. Temperature correction (40°C, 75°C column):
  • Factor = 0.88
  1. Current-carrying conductor adjustment (6 conductors):
  • Factor = 0.80
  1. Combined derating:
Adjusted = 50A × 0.88 × 0.80 = 35.2A

Result: Maximum current = 35A per conductor


Quick Reference: Common Derating Scenarios

4-6 Conductors at Various Temperatures

Wire Size Base 75°C 35°C 40°C 45°C
12 AWG 25A 18.8A 17.6A 16.4A
10 AWG 35A 26.3A 24.6A 23.0A
8 AWG 50A 37.6A 35.2A 32.8A
6 AWG 65A 48.9A 45.8A 42.6A
4 AWG 85A 63.9A 59.8A 55.8A

Based on: 75°C ampacity × temp factor × 0.80 current-carrying conductor adjustment factor

7-9 Conductors at Various Temperatures

Wire Size Base 75°C 35°C 40°C 45°C
12 AWG 25A 16.5A 15.4A 14.4A
10 AWG 35A 23.0A 21.6A 20.1A
8 AWG 50A 32.9A 30.8A 28.7A
6 AWG 65A 42.8A 40.0A 37.3A
4 AWG 85A 55.9A 52.4A 48.9A

Based on: 75°C ampacity × temp factor × 0.70 current-carrying conductor adjustment factor


Special Derating Rules

Continuous Loads (NEC 210.20, 215.3)

For loads operating 3 hours or more continuously (e.g., HVAC, lighting, process equipment):

Conductor ampacity ≥ 125% of continuous load current

Or equivalently — when working from conductor ampacity to maximum allowed load:

Maximum continuous load = conductor adjusted ampacity × 0.80

Important: When both derating and the continuous-load rule apply, the 125% continuous factor is applied after temperature and current-carrying conductor adjustment — it is not a multiplicative derating factor but a minimum conductor sizing requirement:

Required conductor ampacity = (Continuous load × 1.25 + Non-continuous load) ÷ (Temp Factor × Conductor Adjustment Factor)

Example: 20 A continuous load, 40°C ambient, 6 conductors in conduit:

  • Required base ampacity (before derating): (20 × 1.25) = 25 A minimum
  • Derate: 25 A ÷ (0.88 × 0.80) = 25 A ÷ 0.704 = 35.5 A required
  • Select: 8 AWG THHN (50 A at 75°C) — derated to 35.2 A ⊼ 35.5 A, so select 6 AWG (65 A) → derated to 45.8 A > 25 A ✓

Neutral Conductor Derating

3-Phase, 4-Wire Systems:

  • Balanced loads: Neutral doesn't count
  • 50%+ neutral current: Count as current-carrying
  • Harmonic loads (VFDs, computers): Always count neutral

Bundled Cables

For cables bundled >24" without spacing:

  • Apply the same current-carrying conductor adjustment factors when bundled cables require that review
  • 24" minimum spacing = no derating required

Worked Examples

Example 1: Hot Attic Installation

Given:

  • 3 × #10 AWG THHN in attic (50°C ambient)
  • Feeding 30A circuit

Solution:

  1. Base ampacity #10 at 90°C: 40A
  2. Temperature factor (50°C, 90°C): 0.82
  3. Current-carrying conductor adjustment (3 conductors): 1.00
  4. Adjusted: 40A × 0.82 = 32.8A ✓

Result: 32.8A > 30A, installation OK

Example 2: Rooftop HVAC

Given:

  • 3 × #6 AWG THHN on roof
  • Conduit 1" above roof deck
  • 35°C ambient temperature
  • 40A load

Solution:

  1. Rooftop adder (0-1/2" to 3.5"): +22°C
  2. Effective ambient: 35 + 22 = 57°C
  3. Base ampacity #6 at 90°C: 75A
  4. Temperature factor (57°C, 90°C): ~0.68
  5. Adjusted: 75A × 0.68 = 51A ✓

Result: 51A > 40A, installation OK

Example 3: Multiple Circuit Conduit

Given:

  • 12 current-carrying conductors
  • Normal ambient (30°C)
  • Need 20A per circuit
  • Terminals rated 75°C

Solution:

  1. Current-carrying conductor adjustment factor (10-20): 0.50
  2. Temperature factor (30°C): 1.00
  3. Required base ampacity: 20A / 0.50 = 40A
  4. Select: #8 AWG (50A at 75°C) ✓

Verify: 50A × 1.00 × 0.50 = 25A > 20A ✓

Example 4: Hot Location with Many Wires

Given:

  • 8 conductors in conduit
  • 45°C ambient
  • Need 15A per circuit

Solution:

  1. Current-carrying conductor adjustment factor (7-9): 0.70
  2. Temp factor (45°C, 75°C): 0.82
  3. Combined: 0.70 × 0.82 = 0.574
  4. Required base: 15A / 0.574 = 26.1A
  5. Select: #10 AWG (35A at 75°C)

Verify: 35A × 0.574 = 20.1A > 15A ✓


Derating Calculation Workflow

For Any Installation:

  1. Determine load current
  2. Identify conditions:
  • Ambient temperature
  • Number of conductors
  • Continuous vs. non-continuous
  • Terminal ratings
  1. Look up factors:
  • Temperature correction
  • Conduit fill adjustment
  1. Calculate:
Required Ampacity = Load / (Temp × Conductor Adjustment)
  1. Select conductor from NEC tables
  2. Verify the calculation both ways

Common Mistakes to Avoid

Mistake Why It's Wrong Correct Approach
Ignoring terminal ratings May exceed equipment limits Use lower of wire/terminal rating
Not counting harmonics Neutral may overheat Count neutral with harmonic loads
Forgetting rooftop adder Actual temp much higher Add temperature per table
Using 90°C for all Terminals usually 75°C Match to terminal rating

Related Calculators

Calculator Use When...
Ampacity Calculator Full derating calculations
Wire Size Calculator Selecting conductor gauge after derating is known
Conduit Fill Calculator Physical raceway fill
Voltage Drop Calculator Long run sizing

Summary

Temperature Correction:

  • Use NEC Table 310.15(B)(1)
  • Match to insulation temperature rating
  • Add rooftop temperature where applicable

Current-Carrying Conductor Adjustment:

  • 4-6 conductors: 80%
  • 7-9 conductors: 70%
  • 10-20 conductors: 50%

Combined:

Adjusted = Base × Temp Factor × Conductor Adjustment Factor

FAQ

When do I need to derate conductors?

Derate when: ambient exceeds 30°C, more than 3 current-carrying conductors in conduit, rooftop installation, or continuous loads (apply 125% rule).

Do I derate ground wires?

No, equipment grounding conductors are not current-carrying under normal conditions and do not count toward ampacity adjustment or need derating.

Which derating do I apply first?

Apply all factors by multiplication - the order doesn't matter mathematically. Calculate: Base × Temp × Conductor Adjustment = adjusted ampacity.

Can I use 90°C ampacity with 75°C terminals?

No. The limiting factor is the terminal. Use 75°C ampacity values, but you may use 90°C temperature correction factors since the wire itself can handle higher temps.

How do I handle neutral conductors?

For balanced 3-wire circuits, neutral doesn't count. For 4-wire with harmonic loads (LED, computers, VFDs), count neutral as current-carrying.

Tags

NECderatingtemperature correctionconduit fill

Related Calculators

Need to Calculate Something?

Use our electrical calculators to solve your engineering problems quickly and accurately.