Electrical reference chart
Transformer Sizing Chart
Use this transformer sizing chart after the calculator result to document load kVA, primary and secondary current, spare capacity, impedance, inrush, ventilation, and protection review before selecting equipment.
Quick reference table
Transformer sizing starts with kVA math, but the calculator worksheet should also keep load mix, primary and secondary voltage, phase, continuous duty, inrush, impedance, temperature rise, enclosure, ventilation, grounding, overcurrent protection, manufacturer data, adopted NEC rules, and AHJ review visible.
Transformer kVA planning examples
| Load current | 240 V single phase | 208 V three phase | 480 V three phase |
|---|---|---|---|
| 25 A | 6.0 kVA | 9.0 kVA | 20.8 kVA |
| 50 A | 12.0 kVA | 18.0 kVA | 41.6 kVA |
| 100 A | 24.0 kVA | 36.0 kVA | 83.1 kVA |
| 200 A | 48.0 kVA | 72.1 kVA | 166.3 kVA |
Transformer result follow-up worksheet
| After kVA result | Document next | Why it matters |
|---|---|---|
| Calculated kVA near a standard size | Spare capacity, continuous duty, and load diversity | A minimum math result may not be a practical equipment selection |
| Primary and secondary currents differ | Label each side voltage and conductor path | Protection and conductor sizing use side-specific current |
| Motor or nonlinear load present | Inrush, harmonics, K-rated needs, and voltage dip concerns | Load type can affect transformer choice beyond base kVA |
| Indoor or tight location | Temperature rise, enclosure, clearances, and ventilation | Heat and accessibility can control installation planning |
How to use this chart
Convert load to kVA
Start with load current, voltage, phase, and duty context before selecting a transformer kVA rating or standard equipment size.
Label both sides
Keep primary voltage, secondary voltage, primary current, and secondary current separate so breaker and conductor decisions use the correct side.
Add equipment constraints
After the calculator result, document spare capacity, inrush, impedance, temperature rise, enclosure, ventilation, grounding, and manufacturer instructions.
Worksheet checklist
- Record primary and secondary voltagesWrite the serving voltage and load-side voltage so each current calculation uses the correct transformer side.
- Document load mixIdentify motor load, lighting load, continuous load, nonlinear load, expected future capacity, and any load diversity assumption.
- Verify equipment dataUse manufacturer ratings, temperature rise, impedance, ventilation, enclosure, grounding, and protection requirements before selecting equipment.
Common mistakes to avoid
- Selecting transformer kVA from connected load alone without checking load diversity, future capacity, inrush, ventilation, impedance, and equipment rating.
- Mixing primary and secondary current calculations without labeling which voltage side is being used for conductors and protection.
- Treating a standard transformer size as complete without reviewing overcurrent protection, available fault current, temperature rise, and manufacturer installation instructions.
Formula basis
Single phase: kVA = V x A / 1000. Three phase: kVA = 1.732 x V x A / 1000.
- V is the transformer-side voltage used for the current calculation.
- A is load current on the same side of the transformer.
- kVA is apparent power before spare capacity, standard equipment size, or protection review is added.
Worked examples
100 A at 480 V three-phase
1.732 x 480 x 100 / 1000 = about 83.1 kVA before spare capacity, standard transformer rating, ventilation, impedance, or protection is selected.
208 V secondary with 45 kVA transformer
The secondary current is much higher than the primary current when voltage steps down, so conductor and breaker reviews must label which side of the transformer the calculator result represents.
Assumptions
- The table shows apparent power math and does not select a listed transformer size.
- Spare capacity, load diversity, nonlinear loads, inrush, impedance, temperature rise, ventilation, and enclosure choice require project review.
- Primary and secondary protection, grounding, and conductor sizing must be reviewed with the equipment selected for the job.
Code and standard notes
- Verify transformer selection, protection, grounding, ventilation, and equipment installation with the adopted NEC edition, manufacturer data, equipment listing, local amendments, and the Authority Having Jurisdiction (AHJ).
- Coordinate transformer kVA with available fault current, impedance, primary and secondary overcurrent protection, conductor ampacity, and ventilation before procurement.
Related calculators
Transformer Calculator
Screen transformer kVA, turns ratio, full-load current, operating-point losses, and secondary-terminal fault current from basic nameplate inputs.
Power Calculator
Electrical power calculator for DC, single-phase AC, and balanced three-phase AC relationships between voltage, current, real power, apparent power, reactive power, and power factor.
Circuit Breaker Sizing Calculator
Calculate standard breaker sizes for general loads, continuous loads, and simplified motor branch-circuit reviews
Related charts
kVA to Amps Chart
Use this kVA to amps chart: 45 kVA at 480V 3-phase = 54.1A; 15 kVA at 240V 1-phase = 62.5A.
Wire Size Chart
Screen conductor size from calculated load, copper or aluminum material, terminal rating, derating, voltage drop, and equipment notes.
Breaker Size Chart
Plan breaker size from load category, continuous duty, conductor protection, interrupting rating, equipment listing, and calculator result notes.
Frequently asked questions
These answers explain how to use the chart without turning a quick reference into a final design decision.