Planning referenceCode-sensitiveLast reviewed April 29, 2026

Electrical reference chart

Transformer Sizing Chart

Use this transformer sizing chart after the calculator result to document load kVA, primary and secondary current, spare capacity, impedance, inrush, ventilation, and protection review before selecting equipment.

Open calculator

Quick reference table

Transformer sizing starts with kVA math, but the calculator worksheet should also keep load mix, primary and secondary voltage, phase, continuous duty, inrush, impedance, temperature rise, enclosure, ventilation, grounding, overcurrent protection, manufacturer data, adopted NEC rules, and AHJ review visible.

Transformer kVA planning examples

Transformer kVA planning examples
Load current240 V single phase208 V three phase480 V three phase
25 A6.0 kVA9.0 kVA20.8 kVA
50 A12.0 kVA18.0 kVA41.6 kVA
100 A24.0 kVA36.0 kVA83.1 kVA
200 A48.0 kVA72.1 kVA166.3 kVA

Transformer result follow-up worksheet

Transformer result follow-up worksheet
After kVA resultDocument nextWhy it matters
Calculated kVA near a standard sizeSpare capacity, continuous duty, and load diversityA minimum math result may not be a practical equipment selection
Primary and secondary currents differLabel each side voltage and conductor pathProtection and conductor sizing use side-specific current
Motor or nonlinear load presentInrush, harmonics, K-rated needs, and voltage dip concernsLoad type can affect transformer choice beyond base kVA
Indoor or tight locationTemperature rise, enclosure, clearances, and ventilationHeat and accessibility can control installation planning

How to use this chart

1

Convert load to kVA

Start with load current, voltage, phase, and duty context before selecting a transformer kVA rating or standard equipment size.

2

Label both sides

Keep primary voltage, secondary voltage, primary current, and secondary current separate so breaker and conductor decisions use the correct side.

3

Add equipment constraints

After the calculator result, document spare capacity, inrush, impedance, temperature rise, enclosure, ventilation, grounding, and manufacturer instructions.

Formula basis

Single phase: kVA = V x A / 1000. Three phase: kVA = 1.732 x V x A / 1000.

  • V is the transformer-side voltage used for the current calculation.
  • A is load current on the same side of the transformer.
  • kVA is apparent power before spare capacity, standard equipment size, or protection review is added.

Worked examples

100 A at 480 V three-phase

1.732 x 480 x 100 / 1000 = about 83.1 kVA before spare capacity, standard transformer rating, ventilation, impedance, or protection is selected.

208 V secondary with 45 kVA transformer

The secondary current is much higher than the primary current when voltage steps down, so conductor and breaker reviews must label which side of the transformer the calculator result represents.

Frequently asked questions

These answers explain how to use the chart without turning a quick reference into a final design decision.

Is calculated kVA the transformer size I should buy?
No. Calculated kVA is the load basis. Actual transformer selection also considers standard ratings, spare capacity, inrush, impedance, temperature rise, ventilation, and protection.
Should I use primary or secondary voltage?
Use the voltage on the side where the current is known, and label it clearly. Primary and secondary currents are different when the voltages differ.
Why does impedance matter after sizing kVA?
Impedance affects available fault current and voltage behavior. It belongs in the protection and coordination notes even though it is not part of the basic kVA formula.