Wire & Cable calculator
Cable Bundling Derating Calculator
Professional cable bundling derating calculator per NEC 310.15(C)(1). Calculates adjusted ampacity when more than 3 current-carrying conductors are installed together in a raceway, cable, or bundle. Applies both bundling adjustment factors and NEC Table 310.15(B)(1) temperature correction factors for ambient temperatures other than 30°C (86°F). Supports copper and aluminum conductors with 60°C, 75°C, and 90°C insulation ratings.
Updated July 10, 2026
Example Calculations
How to Use
NEC Conductor Derating: Why, When, and How
When current-carrying conductors are bundled together, each conductor generates heat (I²R losses) that warms its neighbors. More conductors in a confined space means more mutual heating and less ability to dissipate that heat to the surrounding air. NEC 310.15(C)(1) requires reducing — "derating" — the allowable ampacity to prevent insulation damage and fire hazards.
NEC 310.15(C)(1) Adjustment Factors
| Current-Carrying Conductors | Adjustment Factor | Effective Ampacity Loss |
|---|---|---|
| 1–3 | 1.00 (100%) | None — baseline condition |
| 4–6 | 0.80 (80%) | 20% reduction |
| 7–9 | 0.70 (70%) | 30% reduction |
| 10–20 | 0.50 (50%) | 50% reduction |
| 21–30 | 0.45 (45%) | 55% reduction |
| 31–40 | 0.40 (40%) | 60% reduction |
| 41+ | 0.35 (35%) | 65% reduction |
Temperature Correction Factors — NEC Table 310.15(B)(1)
Ambient temperature above 30°C (86°F) further reduces allowable ampacity. Apply both factors when conditions require:
| Ambient °C (°F) | 60°C Wire | 75°C Wire | 90°C Wire |
|---|---|---|---|
| 21–25°C (70–77°F) | 1.08 | 1.05 | 1.04 |
| 26–30°C (79–86°F) | 1.00 | 1.00 | 1.00 |
| 31–35°C (88–95°F) | 0.91 | 0.94 | 0.96 |
| 36–40°C (97–104°F) | 0.82 | 0.88 | 0.91 |
| 41–45°C (106–113°F) | 0.71 | 0.82 | 0.87 |
| 46–50°C (115–122°F) | 0.58 | 0.75 | 0.82 |
| 51–55°C (124–131°F) | 0.41 | 0.67 | 0.76 |
The Combined Derating Formula
Derated Ampacity = Base Ampacity × Bundling Factor × Temperature Factor
Worked Example: Control Panel with 12 Current-Carrying Conductors at 45°C
An industrial control panel contains 12 current-carrying #10 AWG THHN conductors. The panel interior reaches 45°C (113°F) during peak operation.
- Base ampacity: #10 THHN copper at 90°C column = 40A (NEC Table 310.16)
- Bundling factor: 12 conductors → 0.50 (50%)
- Temperature factor: 45°C for 90°C wire → 0.87
- Derated ampacity: 40A × 0.50 × 0.87 = 17.4A
This is a dramatic reduction — from 40A to 17.4A, a 56.5% loss. The 90°C wire rating helps here: if using 75°C-rated THWN wire (base 35A), the derated value would be 35 × 0.50 × 0.82 = 14.4A — even worse. This is why the NEC 310.15(B)(2) "90°C trick" is so valuable: rate the wire at the 90°C column for derating purposes, then limit the final ampacity to the 75°C terminal rating.
What Counts as a "Current-Carrying Conductor"?
This is the most common source of confusion in derating calculations:
| Conductor Type | Count It? | NEC Reference |
|---|---|---|
| Phase conductors (L1, L2, L3) | ✅ Always | 310.15(F) |
| Neutral — balanced linear loads | ❌ No | 310.15(F)(1) |
| Neutral — nonlinear loads (3rd harmonic) | ✅ Yes | 310.15(F)(2) |
| Equipment grounding conductor | ❌ No | 310.15(F) |
| Control wires (Class 1) | ✅ Yes | 310.15(C)(1) |
| Travelers (3-way/4-way switches) | ✅ Yes | Only one counts per switch loop |
Bundles Shorter Than 24 Inches
NEC 310.15(C)(1) exempts conductor bundles that are 24 inches (600mm) or shorter from derating. This is often relevant at panel boards, junction boxes, and wireways where conductors are bundled only at entry/exit points. However, the 24-inch exemption does not apply in raceways — if conductors are in conduit, they must be derated regardless of conduit length.
Common Applications
More applications. Open to review 5 additional use cases.
Frequently Asked Questions
When do I need to derate cables for bundling per NEC?
Do I count neutral conductors for bundling derating?
Can I use the 90°C wire rating for derating and then limit to 75°C for terminals?
How does cable tray derating differ from conduit derating?
What happens if I need to apply both bundling and temperature derating simultaneously?
Related Calculators
Handle conductor gauge selection from load current, standard OCPD, and voltage drop after ampacity and raceway constraints are known.
Individual conductor ampacity and derating per NEC 310.16 with ambient-temperature correction, current-carrying conductor adjustment, and terminal-rating limits.
Use for cable assemblies such as NM-B, MC, and AC/BX where the jacketed cable rules differ from individual conductors in raceway.
Calculate voltage drop in conductors
Screen conductor ampacity derating from ambient temperature, more than three current-carrying conductors, and the governing terminal-temperature limit.
Check conduit fill, conductor count, and raceway loading against NEC-style limits.