Wire & Cable calculator
Cable Ampacity Calculator
Multi-conductor cable ampacity calculator for assembled cables with multiple insulated conductors in a single jacket. Use it for Type NM-B, Type MC, and Type AC screening with NEC reference context, then verify against the adopted code edition and equipment terminations.
Updated August 5, 2026
Example Calculations
More examples. Open to review 1 additional calculation example.
How to Use
NEC Multi-Conductor Cable Ampacity Standards
Cable vs Conductor: Multi-conductor cables contain 2+ insulated conductors in a single jacket/armor. Ampacity differs from individual conductors due to thermal characteristics and NEC application rules.
Cable Type Comparison: NM-B vs MC vs AC (Critical Selection Guide)
| Feature | Type NM-B (Romex) | Type MC (Metal-Clad) | Type AC (BX) |
|---|---|---|---|
| Temperature Rating | Use the 60°C basis unless the adopted NEC edition, product marking, and installation method allow otherwise | 90°C (THHN/XHHW) | 60°C typical |
| Max Ampacity | Common residential branch-circuit range; verify Article 334 limits for the adopted edition | Use the applicable ampacity table, cable marking, and terminal temperature rating | Typically ≤30A branch circuits |
| Use Scope to Verify | Dry-location residential use when Article 334, the building type, and local amendments allow it | Review Article 330, product marking, support, exposure, and location limits | Review Article 320, existing-work conditions, support, and connector requirements |
| Commercial Review | Verify Article 334 scope before using NM-B in nonresidential work | Verify Article 330 scope, listing, and project conditions | Verify Article 320 scope; MC is often reviewed for new commercial runs |
| Mechanical Protection | PVC jacket only | Aluminum/steel armor | Galvanized steel armor |
| Typical Cost (12/2) | $0.40-0.60/ft | $1.20-1.80/ft | $0.90-1.20/ft |
| Best For | Residential branch circuits | Commercial, high-ampacity feeders | Residential retrofit (old work) |
Selection screen: Start with NM-B only when the project is a dry-location residential branch-circuit use that Article 334 and local amendments allow. Review Type MC when the project needs commercial scope, mechanical protection, feeders, exposed runs, or a 90°C derating starting point. Treat Type AC as a separate Article 320 review rather than an automatic substitute for MC.
Type NM-B Cable Ampacity (Romex) - NEC 334.80
| Cable Size | Conductors | Ampacity (60°C) | Max Breaker | Typical Use |
|---|---|---|---|---|
| 14/2 NM-B | 14 AWG Cu | 15A | 15A | Lighting, receptacles |
| 12/2 NM-B | 12 AWG Cu | 20A | 20A | General receptacles, kitchen |
| 10/2 NM-B | 10 AWG Cu | 30A | 30A | Dryer, water heater |
| 10/3 NM-B | 10 AWG Cu | 30A | 30A | Electric range, MWBC |
| 8/3 NM-B | 8 AWG Cu | 40A | 40A | Electric range (50A receptacle) |
| 6/3 NM-B | 6 AWG Cu | 55A | 55A | Subpanel feeders |
NM-B restrictions to verify: Review Article 334 in the NEC edition adopted for the project, the cable marking, the building type, exposed or damp/wet-location limits, and local amendments before using an NM-B result as the final cable selection.
Type MC Cable Ampacity (Metal-Clad) - NEC 330.80
| Cable Size | Insulation | Ampacity | Applications |
|---|---|---|---|
| 12/2 MC-THHN | 90°C (THHN) | 30A (use 25A @ 75°C term) | Commercial, exposed areas |
| 10/3 MC-THHN | 90°C (THHN) | 40A (use 35A @ 75°C term) | Feeders, industrial |
| 8/4 MC-THHN | 90°C (THHN) | 55A (use 50A @ 75°C term) | Subpanel feeders |
| 6/4 MC-THHN | 90°C (THHN) | 75A (use 65A @ 75°C term) | Large feeders, 60A circuits |
MC cable review points: 90°C insulation can provide a higher derating starting point, armor adds mechanical protection, and Article 330 may fit commercial or industrial routing when the listed cable, supports, fittings, location, and equipment terminations are suitable. Still apply terminal limits, overcurrent protection, load rules, and the adopted NEC edition before final selection.
Type AC Cable Ampacity (BX/Armored) - NEC 320.80
| Cable Size | Ampacity (60°C) | Max Use |
|---|---|---|
| 14/2 AC | 15A | Lighting circuits |
| 12/2 AC | 20A | General circuits |
| 10/2 AC | 30A | Limited to branch circuits |
AC Cable Limitations: Type AC (BX) typically 60°C rated, not suitable for high-ampacity feeders. Consider Type MC for commercial/industrial installations requiring >30A capacity.
For conductor ampacity without cable assembly restrictions, use NEC Ampacity Calculator. For voltage drop analysis, use Voltage Drop Calculator. For final conductor sizing, use Wire Size Calculator. Keep conduit-fill questions on the Conduit Fill Calculator; this page is for cable assemblies, not raceway occupancy.
After confirming ampacity, check that the conductor maintains voltage within acceptable limits—see the Voltage Drop Formulas Guide for NEC-based analysis.
Common Applications
More applications. Open to review 5 additional use cases.
Frequently Asked Questions
Why does NM-B cable usually use the 60°C ampacity basis?
When using 90°C rated MC cable, why should terminal temperature limits be checked?
What cable should I use for Multi-Wire Branch Circuits (MWBC) and why does cable type matter?
How do I apply temperature derating to NM-B cable in hot attics and why is it more severe than MC cable?
Related Calculators
Individual conductor ampacity and derating per NEC 310.16 with ambient-temperature correction, current-carrying conductor adjustment, and terminal-rating limits.
Handle conductor gauge selection from load current, standard OCPD, and voltage drop after ampacity and raceway constraints are known.
Calculate voltage drop in conductors
Check conduit fill, conductor count, and raceway loading against NEC-style limits.
Convert between AWG, mm², and circular mils for conductor sizing and documentation.
NEC-oriented standard breaker review-point screen with simplified conductor protection checks.