Wire & Cable calculator

Cable Ampacity Calculator

This cable-ampacity screen evaluates conductor size, material, installation method, insulation, ambient temperature, current-carrying conductor count, and optional load or voltage-drop inputs. It does not identify a listed NM-B, MC, or AC product by itself; use the result with the cable marking, adopted code edition, equipment terminations, and installation conditions.

Updated October 29, 2026

Calculator Inputs

Field notes

Calculation Results

Enter values above to see calculation results

Opens in a new tabOpens in a new tabOpens in a new tab
Calculation history

Example Calculations

Cable-assembly ampacity lookupUse the implemented lookup mode with a copper conductor in a cable-assembly installation method. Product marking and terminal checks remain outside the calculator.InputsCalculation Mode: Ampacity lookupWire Gauge: 12Wire Type: CopperInstallation Method: Cable or conductorAmbient Temperature: 30Current-Carrying Conductors: 3Current-Carrying Conductor Factor: 40Insulation Type: THHN/THWN-2
Cable-assembly derating screenUse the derating mode when ambient temperature and current-carrying conductor count must be combined with the selected conductor data.InputsCalculation Mode: Derating calculationWire Gauge: 10Wire Type: CopperInstallation Method: Cable or conductorAmbient Temperature: 40Current-Carrying Conductors: 6Current-Carrying Conductor Factor: 40Insulation Type: THHN/THWN-2
Cable voltage-drop checkUse the voltage-drop mode when the run length, load current, and system voltage are known.InputsCalculation Mode: Voltage Drop CheckWire Gauge: 12Wire Type: CopperInstallation Method: Cable or conductorAmbient Temperature: 30Current-Carrying Conductors: 3Cable Length: 100Load Current: 20Voltage Rating: 120Current-Carrying Conductor Factor: 40Insulation Type: THHN/THWN-2

How to Use

NEC Multi-Conductor Cable Ampacity Standards

Cable vs Conductor: Multi-conductor cables contain 2+ insulated conductors in a single jacket/armor. Ampacity differs from individual conductors due to thermal characteristics and NEC application rules.

Calculator input boundary: Select the installation method (raceway/conduit, cable assembly, direct burial, free air, or cable tray), conductor gauge and material, ambient temperature, current-carrying conductor count, and insulation type. The wire-sizing, voltage-drop, and complete-analysis modes also use the load current, cable length, and system voltage fields. The tool does not have a NM-B/MC/AC product selector or a terminal-rating input, so those product and termination checks remain part of the installation review.

Cable Type Comparison: NM-B vs MC vs AC (Critical Selection Guide)

Feature Type NM-B (Romex) Type MC (Metal-Clad) Type AC (BX)
Temperature Rating Use the 60°C basis unless the adopted NEC edition, product marking, and installation method allow otherwise 90°C (THHN/XHHW) 60°C typical
Max Ampacity Common residential branch-circuit range; verify Article 334 limits for the adopted edition Use the applicable ampacity table, cable marking, and terminal temperature rating Typically ≤30A branch circuits
Use Scope to Verify Dry-location residential use when Article 334, the building type, and local amendments allow it Review Article 330, product marking, support, exposure, and location limits Review Article 320, existing-work conditions, support, and connector requirements
Commercial Review Verify Article 334 scope before using NM-B in nonresidential work Verify Article 330 scope, listing, and project conditions Verify Article 320 scope; MC is often reviewed for new commercial runs
Mechanical Protection PVC jacket only Aluminum/steel armor Galvanized steel armor
Best For Residential branch circuits Commercial, high-ampacity feeders Residential retrofit (old work)

Selection screen: Start with NM-B only when the project is a dry-location residential branch-circuit use that Article 334 and local amendments allow. Review Type MC when the project needs commercial scope, mechanical protection, feeders, exposed runs, or a 90°C derating starting point. Treat Type AC as a separate Article 320 review rather than an automatic substitute for MC.

Type NM-B Cable Ampacity (Romex) - NEC 334.80

Cable Size Conductors Ampacity (60°C) Max Breaker Typical Use
14/2 NM-B 14 AWG Cu 15A 15A Lighting, receptacles
12/2 NM-B 12 AWG Cu 20A 20A General receptacles, kitchen
10/2 NM-B 10 AWG Cu 30A 30A Dryer, water heater
10/3 NM-B 10 AWG Cu 30A 30A Electric range, MWBC
8/3 NM-B 8 AWG Cu 40A 40A Electric range (50A receptacle)
6/3 NM-B 6 AWG Cu 55A 55A Subpanel feeders

NM-B restrictions to verify: Review Article 334 in the NEC edition adopted for the project, the cable marking, the building type, exposed or damp/wet-location limits, and local amendments before using an NM-B result as the final cable selection.

Type MC Cable Ampacity (Metal-Clad) - NEC 330.80

Cable Size Insulation Ampacity Applications
12/2 MC-THHN 90°C (THHN) 30A (use 25A @ 75°C term) Commercial, exposed areas
10/3 MC-THHN 90°C (THHN) 40A (use 35A @ 75°C term) Feeders, industrial
8/4 MC-THHN 90°C (THHN) 55A (use 50A @ 75°C term) Subpanel feeders
6/4 MC-THHN 90°C (THHN) 75A (use 65A @ 75°C term) Large feeders, 60A circuits

MC cable review points: 90°C insulation can provide a higher derating starting point, armor adds mechanical protection, and Article 330 may fit commercial or industrial routing when the listed cable, supports, fittings, location, and equipment terminations are suitable. Still apply terminal limits, overcurrent protection, load rules, and the adopted NEC edition before final selection.

Type AC Cable Ampacity (BX/Armored) - NEC 320.80

Cable Size Ampacity (60°C) Max Use
14/2 AC 15A Lighting circuits
12/2 AC 20A General circuits
10/2 AC 30A Limited to branch circuits

AC Cable Limitations: Type AC (BX) typically 60°C rated, not suitable for high-ampacity feeders. Consider Type MC for commercial/industrial installations requiring >30A capacity.

For conductor ampacity without cable assembly restrictions, use the NEC Ampacity Calculator. For voltage drop analysis, use the Voltage Drop Calculator. For final conductor sizing, use the Wire Size Calculator. Move to the Breaker Sizing Calculator only after the load current and final conductor basis are known. Keep conduit-fill questions on the Conduit Fill Calculator; this page is for cable assemblies, not raceway occupancy.

After confirming ampacity, check that the conductor maintains voltage within acceptable limits—see the Voltage Drop Formulas Guide for NEC-based analysis.

Common Applications

Cable-assembly screening - Review conductor size, material, installation method, insulation, ambient temperature, and conductor count together
Wire sizing - Use the load-current mode when a conductor size must be screened for a known load
Voltage-drop review - Use the cable length, load current, and system-voltage fields when distance controls the result
Cable bundling analysis - Use the current-carrying conductor count for the modeled adjustment factor
Adopted-Code Cable Review - Screen cable type against occupancy, location, product marking, support, and installation limits before final selection

Frequently Asked Questions

Does this calculator choose NM-B, MC, or AC by name?
No. The calculator screens conductor and installation inputs, including a cable-assembly installation method, but it does not select a listed product or verify its marking, fittings, location limits, or terminal rating. Match the screen to the actual cable documentation and the adopted code path before final selection.
Why does NM-B cable usually use the 60°C ampacity basis?
Use the 60°C ampacity basis for Type NM-B unless the adopted NEC edition, cable marking, equipment terminations, and installation details support a different review path. The calculator separates conductor table values from the cable-assembly and terminal limits so a larger feeder is not selected from the 75°C or 90°C column alone. For higher-current feeders, compare NM-B with a listed MC cable or individual conductors in raceway after checking Article 334 limits, local amendments, and the equipment termination ratings.
When using 90°C rated MC cable, why should terminal temperature limits be checked?
NEC 110.14(C) makes the equipment termination rating part of the final ampacity review. A 90°C insulation rating can be useful as a starting point for temperature or bundling corrections, but the final result still needs to be compared with the marked terminal rating, the overcurrent device, the load type, and the adopted NEC edition. For example, a 90°C starting value may remain useful after ambient correction while the final branch-circuit review is still limited by 60°C or 75°C equipment terminations.
What cable should I use for Multi-Wire Branch Circuits (MWBC) and why does cable type matter?
An MWBC review normally starts with a 3-wire cable or raceway grouping that keeps the ungrounded conductors and shared neutral together. Check NEC 210.4, simultaneous disconnect requirements, neutral sizing, conductor grouping, and the equipment layout before selecting 12/3 NM-B, 10/3 NM-B, MC, or individual conductors in raceway. Separate cable runs need a documented design and inspection basis because conductor grouping and neutral current can become safety issues.
How do I apply temperature derating to NM-B cable in hot attics and why is it more severe than MC cable?
Hot locations make the insulation temperature column important. A 12/2 NM-B screen at 50°C starts from the 60°C basis and may fall below the intended circuit load after correction, while a listed MC cable with 90°C insulated conductors may have more derating headroom before the final terminal check. Use the calculator result as a prompt to compare conductor size, cable type, ambient assumptions, terminal rating, and the adopted NEC correction table before deciding whether to upsize or change wiring method.

Related Calculators

Browse all calculators