Safety & Protection calculator
NGR Calculator
This neutral grounding resistor (NGR) calculator is designed for electrical engineers and protection specialists who need to size NGRs for medium and high voltage systems. Given system voltage and desired ground fault current limit, the calculator computes the required NGR resistance using the fundamental relationship R = V_LN / I_fault per IEEE 142 (Green Book). Additional modes handle power dissipation analysis, thermal rating selection, system charging current comparison, and complete NGR specification. The tool supports common voltages from 480V to 69kV and fault currents from 5A to 400A, covering both generator and transformer neutral grounding applications. All outputs should be verified against IEEE 142, IEEE C62.92, NEMA GR-1, and applicable NEC articles before specifying safety-critical equipment.
Updated August 4, 2026
Example Calculations
How to Use
How to Size a Neutral Grounding Resistor (NGR) per IEEE 142
This calculator helps you determine the correct NGR resistance, power rating, and thermal capacity for medium and high voltage systems using high-resistance grounding (HRG). It applies the IEEE 142 methodology used by electrical engineers worldwide.
Quick Reference: Common NGR Values for 10A Fault Limit
| System Voltage (L-L) | V_LN | NGR Resistance | Power @ 10A |
|---|---|---|---|
| 2.4 kV | 1,386 V | 139 Ω | 1.4 kW |
| 4.16 kV | 2,402 V | 240 Ω | 2.4 kW |
| 6.6 kV | 3,811 V | 381 Ω | 3.8 kW |
| 11 kV | 6,351 V | 635 Ω | 6.4 kW |
| 13.8 kV | 7,967 V | 797 Ω | 8.0 kW |
| 22 kV | 12,702 V | 1,270 Ω | 12.7 kW |
| 33 kV | 19,053 V | 1,905 Ω | 19.1 kW |
Step 1: Select Calculation Mode
- NGR Resistance Sizing – Primary mode: enter voltage and desired fault current to get NGR resistance.
- Fault Current Analysis – Compare NGR-limited current to bolted fault current.
- Power Rating – Calculate thermal capacity needed based on fault duration.
- Charging Current Analysis – Verify NGR current exceeds system charging current (critical for HRG).
- Complete Design – Full NGR specification with all parameters.
Step 2: Enter System Parameters
- System Voltage (L-L) – Select your line-to-line voltage (480V to 69kV).
- Desired Fault Current – Typical values: 5-25A for generators, 25-400A for transformers.
- Fault Duration – For power rating: 10 seconds is standard, 60 seconds for extended.
Step 3: Interpret Results
- NGR Resistance – Calculated as R = V_LN / I_fault per IEEE 142.
- Power Rating – P = I² × R, must be rated for specified duration.
- Thermal Capacity – Energy in kJ or kW-seconds the NGR must absorb.
- Charging Current Ratio – Must be <100% for proper HRG operation.
Core Formula (IEEE 142)
R_NGR = V_LN / I_fault = (V_LL / √3) / I_fault Where: V_LL = Line-to-line system voltage V_LN = Line-to-neutral voltage (phase voltage) I_fault = Desired ground fault current limit Example (13.8kV, 10A limit): R = (13,800 / √3) / 10 R = 7,967 / 10 R = 797 Ω
Common Applications
More applications. Open to review 4 additional use cases.
Frequently Asked Questions
What is the NGR resistance formula?
What is the typical fault current for generator NGR?
Why must NGR current exceed charging current?
How do I determine NGR power rating?
What is the difference between high-resistance and low-resistance grounding?
Related Calculators
Screen adjusted incident energy and approximate arc flash boundary from a known base case.
Open the electrical safety for related safety & protection review.
Review core IEEE 1584 scope, task-distance incident energy, and published boundary position from a known study case.
Convert watts and lumens, solve lm/W, and estimate room lumens from area and target illuminance.
Screen available fault current from transformer impedance, feeder impedance, or known source impedance.
NEC-oriented standard breaker review-point screen with simplified conductor protection checks.