Safety & Protection calculator
Ground Fault Loop Calculator
Calculate ground fault loop impedance (Zs) and prospective fault current. For the 120 V example with a 50 kVA transformer, 100 ft of #12 copper line conductor and #12 EGC, plus 50 mΩ connection resistance, Zs is 0.453 Ω and prospective fault current is 265 A. Use the result for protective-device and equipment-grounding review against the adopted NEC edition, equipment documentation, and AHJ requirements.
Updated June 21, 2026
Example Calculations
120V Residential, 100 ft
Typical home branch circuit.
- System Voltage: 120 V
- Transformer Rating: 50
- Conductor Size: 12
- Circuit Length: 100
- Equipment Grounding Conductor Size: 12
How to Use
Quick Answer
What is ground fault loop impedance?
Zs = Z_transformer + Z_line + Z_EGC + Z_connections
Ground fault loop impedance determines how much fault current will flow during a ground fault. Higher impedance = less fault current = slower or failed protective device operation.
| Zs (Ω) | Fault Current @ 120V | Status |
|---|---|---|
| 0.1 | 1,200A | Excellent |
| 0.5 | 240A | Good |
| 1.0 | 120A | Check CB rating |
| 2.0 | 60A | May not trip instantaneously |
NEC Requirements
NEC 250.4 - Effective Ground Fault Current Path
The ground fault path must have sufficiently low impedance to:
- Facilitate operation of overcurrent protective device
- Limit voltage to ground during fault condition
- Clear the fault in minimum time
Fault Current Rule of Thumb
Fault current should be ≥ 5× the circuit breaker rating for instantaneous trip.
Example: 20A CB needs at least 100A fault current for fast trip.
Ground-Fault Loop Review Notes
| Review Item | What to Check |
|---|---|
| Loop impedance | Line conductor, EGC, transformer impedance, and connection resistance |
| Available fault current | Compare the calculated current with breaker and equipment ratings |
| Protective device | Review the time-current curve or manufacturer trip data |
For EGC sizing, see Wire Size Calculator with NEC 250.122 references.
Common Applications
Circuit Verification - Confirm protective devices will operate on fault
Long Run Analysis - Verify impedance on extended circuits
Safety Review - Review NEC 250.4, project criteria, and device documentation
Troubleshooting - Diagnose nuisance tripping or non-tripping
Design Validation - Pre-construction fault analysis
Frequently Asked Questions
How do I measure ground fault loop impedance?
What is a good loop impedance value?
Why is my fault loop impedance too high?
Does GFCI protection change the requirements?
How often should ground fault loop impedance be tested?
Related Calculators
Grounding Resistance Calculator
Estimate driven-rod and multi-rod resistance from soil resistivity, rod geometry, and spacing.
ExploreWire Size Calculator
Handle conductor gauge selection from load current, standard OCPD, and voltage drop after ampacity and raceway constraints are known.
ExploreShort Circuit Calculator
Screen available fault current from transformer impedance, feeder impedance, or known source impedance.
ExploreCircuit Breaker Sizing Calculator
NEC-oriented standard breaker review-point screen with simplified conductor protection checks.
ExploreArc Flash Calculator
Screen adjusted incident energy and approximate arc flash boundary from a known base case.
ExploreElectrical Safety
Open the electrical safety for related safety & protection review.
Explore