Safety & Protection calculator
Fuse Sizing Calculator
Use this calculator as a fuse sizing planning screen. A 65 A motor FLC with a dual-element time-delay fuse gives 113.75 A calculated, 110 A at-or-below, and 125 A to review before final equipment and code checks.
Updated June 2, 2026
A 65A motor branch fuse screen with a dual-element time-delay family calculates 113.75A at 175%, so 110A is the largest common standard fuse size at or below the calculation and 125A is the first standard-size review point.
Calculated fuse value = current basis x code percentage | Keep the calculated value separate from any next-standard-size review.
Choose general load, motor branch, transformer primary, or capacitor-bank boundary mode below to screen the fuse basis before final code and equipment review
Calculator Inputs
Calculation Results
Enter values above to see calculation results
Example Calculations
Motor branch time-delay fuse
Screen a 65 A motor FLC basis with a dual-element time-delay fuse family.
- Calculation Mode: Motor Branch
- Load Current: 65
- Fuse Family: Dual Element
How to Use
What this fuse sizing calculator does
This page keeps the fuse sizing basis visible. It does not hide all code paths behind a single "recommended fuse" label. Instead, it shows the calculated ampere value and separates the standard-size review step so you can confirm whether the adopted NEC path allows the next higher standard size.
Supported sizing screens
- General branch or feeder load: a 125% planning screen from the entered current basis.
- Motor branch fuse: a motor branch short-circuit and ground-fault fuse screen using 175% for time-delay families and 300% for non-time-delay style review.
- Transformer primary fuse: a primary fuse planning screen from transformer primary current, with primary-only and primary-plus-secondary protection arrangements kept separate.
- Capacitor bank boundary: a 135% capacitor-current basis for conductor and disconnect planning, with a clear warning that the actual fuse must be selected from manufacturer data, inrush behavior, and the adopted code path.
How to read the output
The calculator returns two standard-size values:
- Standard size at or below calculation: the largest common standard fuse ampere rating that does not exceed the calculated value.
- First standard size for review: the next common standard rating. This value is not automatically approved; it is the first value to check if the specific code path allows a next higher standard size.
Motor example
A motor branch circuit is screened with 65 A as the motor FLC basis and a dual-element time-delay fuse family.
- Sizing percentage: 175%
- Calculated fuse value: 65 A x 1.75 = 113.75 A
- Standard size at or below calculation: 110 A
- First standard size for review: 125 A
This page does not size motor overload protection. Motor overload protection, conductor ampacity, available fault current, SCCR, fuse class, fuse holder, and manufacturer instructions still need their own review.
Transformer example
A transformer primary is screened with 90.2 A of primary current.
- Sizing percentage: 125%
- Calculated fuse value: 112.75 A
- Standard size at or below calculation: 110 A
- First standard size for review: 125 A
Whether that first standard size is acceptable depends on the actual transformer protection arrangement, voltage class, primary current threshold, and adopted transformer rule. The calculator deliberately leaves that decision visible.
When the transformer arrangement includes both primary and secondary protection, the primary-side screen uses a 250% review basis. That does not size the secondary overcurrent protection or secondary conductors.
Capacitor bank boundary
The capacitor-bank mode is not a one-number fuse recommendation. It shows the 135% capacitor current basis used for conductor and disconnect planning, then marks the fuse decision as a separate review. Capacitor fuses must be kept as low as practicable while still handling capacitor inrush, harmonic current, available fault current, the fuse class, the holder, and the manufacturer data.
Fuse class is not the same as fuse ampere rating
Class J, RK1, RK5, CC, and T fuses have different physical rejection features, interrupting ratings, time-current behavior, and current-limiting performance. Those features matter for equipment compatibility and SCCR, but they do not remove the need to verify the ampere rating against the correct code basis.
Common Applications
Screen a fuse ampere rating before checking a specific fuse class and holder
Review motor branch time-delay or non-time-delay fuse sizing from a motor FLC basis
Check transformer primary fuse planning values before confirming the protection arrangement
Use capacitor-bank mode as a boundary check before manufacturer fuse selection
Separate calculated fuse value from standard-size review to avoid hidden over-sizing
Prepare notes for equipment listing, available fault current, and SCCR review
Frequently Asked Questions
Why does the calculator avoid a single recommended fuse size?
Can I always use the next higher standard fuse size?
Does the motor mode size overload protection?
Does the fuse class change the calculated ampere value?
What else must be checked before installing a fuse?
Related Calculators
Circuit Breaker Sizing Calculator
NEC-oriented standard breaker review-point screen with simplified conductor protection checks.
ExploreMotor Branch Protection Calculator
Screen NEC Article 430 motor branch-circuit short-circuit and ground-fault protective device sizing.
ExploreShort Circuit Calculator
Screen available fault current from transformer impedance, feeder impedance, or known source impedance.
ExploreProtection Coordination Calculator
One-point screen for coordination time margin, published selective current, and instantaneous pickup checks.
ExploreArc Flash Calculator
Screen adjusted incident energy and approximate arc flash boundary from a known base case.
ExploreElectrical Safety
Open the electrical safety for related safety & protection review.
Explore