NEC Quick Reference

Locate the articles, tables, and workflow checkpoints U.S. electricians and electrical designers open most often before turning to the adopted edition of NFPA 70.

Updated April 24, 2026

Use this page to locate the right section, not to replace the code text. The adopted edition of NFPA 70 and any local amendments remain the enforceable source for final design, installation, inspection, and acceptance decisions.

The adopted edition of NFPA 70 and any local amendments remain the enforceable source for final design, installation, inspection, and acceptance decisions.

Core Installation Articles

Art. 100

Definitions

Start here when a term such as bonding, grounded conductor, readily accessible, or service point changes the meaning of the rule you are reading.

Art. 110

Requirements for Electrical Installations

Use for equipment approval, working space, terminations, and the general installation-quality rules that show up across the code.

Art. 210

Branch Circuits

Open this article when branch-circuit layout, required receptacles, or GFCI and AFCI screening drives the design decision.

Art. 215

Feeders

Use for feeder minimum rating, conductor sizing basis, and coordination with feeder overcurrent protection.

Art. 220

Load Calculations

Start here when service or feeder sizing depends on demand factors, unit loads, appliance diversity, or dwelling/commercial load methods.

Art. 230

Services

Service conductors, service disconnecting means, and the basic service arrangement are typically screened here first.

Art. 240

Overcurrent Protection

Use for breaker or fuse rating choices, conductor-protection limits, and many tap-rule or small-conductor questions.

Art. 250

Grounding and Bonding

The main starting point for system grounding, bonding jumpers, grounding electrode systems, and effective fault-current paths.

Wiring Methods and Conductor Rules

Art. 300

General Requirements

Use for routing, support, protection, and other general wiring-method rules that apply before you reach a specific raceway or cable article.

Art. 310

Conductors and Ampacity Rules

This is where conductor selection, ampacity basis, insulation temperature limits, and adjustment or correction lookups come together.

Sec. 314.16

Box Fill

Open this section for box volume allowances and conductor counts in outlet, device, pull, and junction boxes.

Art. 334

Type NM Cable

A common dwelling-unit starting point when you need the permitted uses and installation rules for Type NM cable.

Equipment and Utilization Articles

Art. 404

Switches

Use for switch rating, grounding, and installation basics in branch-circuit work.

Art. 406

Receptacles and Cord Connectors

Useful for receptacle type, rating, tamper-resistant selection, and many location-based device requirements.

Art. 408

Panelboards and Similar Equipment

Start here for panelboard arrangement, identification, and distribution-equipment rules in common building work.

Art. 422

Appliances

Use for fixed appliances, disconnecting means, and branch-circuit coordination around appliance loads.

Art. 430

Motors, Motor Circuits, and Controllers

The main starting point for motor conductors, overload protection, short-circuit protection, and controller rules.

Art. 440

Air-Conditioning and Refrigerating Equipment

Use when HVAC or refrigerating equipment drives conductor sizing, disconnecting means, or equipment protection choices.

Special Occupancies and Systems

Art. 517

Health Care Facilities

A common starting point for patient-care spaces, essential electrical systems, and related facility rules.

Art. 680

Pools, Fountains, and Similar Installations

Use for bonding, GFCI, wiring, and equipment around pools, spas, hot tubs, and fountains.

Art. 690

Solar Photovoltaic (PV) Systems

Open this article for PV source circuits, disconnecting means, rapid shutdown, and grounding or bonding review.

Common NEC Tables and Sections

Table 310.16

Conductor Ampacity Lookup

A common starting table for conductor ampacity under 2000 volts after you confirm conductor type, temperature rating, and installation conditions.

Art. 310 tables

Adjustment and Correction Lookups

Use the temperature-correction and conductor-adjustment lookups in Article 310 alongside the base ampacity table.

Table 250.66

Grounding Electrode Conductor Sizing

Sizes the grounding electrode conductor from the largest service or feeder conductors in the installation.

Table 250.122

Equipment Grounding Conductor Sizing

Sets the minimum equipment grounding conductor size from the circuit overcurrent device.

Table 220.12

General Lighting Loads by Occupancy

Used when service or feeder calculations start from floor area and occupancy-based unit lighting loads.

Sec. 314.16

Box Volume Allowances

The common box-fill starting point for conductor allowances and standard box volume review.

Table 430.250

Three-Phase Motor Full-Load Current

Frequently used in motor conductor and protection workflows when a three-phase motor is being screened.